SJ200 Inverter
Output Function Summary Table – This table shows all ten functions for the logical outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page
|
|
| Output Function Summary Table |
|
|
| ||
|
|
|
|
|
|
|
|
|
| Option | Terminal | Function Name |
| Description |
|
|
|
| Code | Symbol |
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 00 | RUN | Run Signal | ON | when inverter is in Run Mode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | when inverter is in Stop Mode |
|
|
|
|
|
|
|
|
|
|
|
|
| 01 | FA1 | Frequency Arrival | ON | when output to motor is at the set frequency |
|
|
|
|
|
| Type 1 – Constant |
|
|
|
|
|
|
|
| OFF | when output to motor is OFF, or in any accelera- |
|
|
| |
|
|
| Speed |
|
|
| ||
|
|
|
| tion or deceleration ramp |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 02 | FA2 | Frequency Arrival | ON | when output to motor is at or above the set |
|
|
|
|
|
| Type 2 – Over- |
| frequency, even if in accel. or decel. ramps |
|
|
|
|
|
| frequency |
|
|
|
|
|
|
|
| OFF | when output to motor is OFF, or at a level below |
|
|
| |
|
|
|
|
|
|
| ||
|
|
|
|
| the set frequency |
|
|
|
|
|
|
|
|
|
|
|
|
| 03 | OL | Overload Advance | ON | when output current is more than the set thresh- |
|
|
|
|
|
| ||||||
|
|
| Notice Signal |
| old for the overload signal |
| ParametersDrive |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when output current is less than the set threshold |
| Configuring | |
|
|
|
|
| for the overload signal |
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 04 | OD | Output Deviation for | ON | when PID error is more than the set threshold for |
|
|
|
|
|
| PID Control |
| the deviation signal |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | when PID error is less than the set threshold for |
|
|
|
|
|
|
|
| the deviation signal |
|
|
|
|
|
|
|
|
|
|
|
|
| 05 | AL | Alarm Signal | ON | when an alarm signal has occurred and has not |
|
|
|
|
|
|
|
| been cleared |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | when no alarm has occurred since the last |
|
|
|
|
|
|
|
| clearing of alarm(s) |
|
|
|
|
|
|
|
|
|
|
|
|
| 06 | Dc | Analog Input | ON | when the [O] input value < B082 setting (signal |
|
|
|
|
|
| Disconnect Detect |
| loss detected), or the [OI] input current < 4mA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | when no signal loss is detected |
|
|
|
|
|
|
|
|
|
|
|
|
| 07 | FBV | PID Second Stage | ON | Transitions to ON when the inverter is in RUN |
|
|
|
|
|
| Output |
| Mode and the PID Process Variable (PV) is less |
|
|
|
|
|
|
|
| than the Feedback Low Limit (C053) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | Transitions to OFF the PID Feedback Value (PV) |
|
|
|
|
|
|
|
| exceeds the PID High Limit (C052), and transi- |
|
|
|
|
|
|
|
| tions to OFF when the inverter goes from Run |
|
|
|
|
|
|
|
| Mode to Stop Mode. |
|
|
|
|
|
|
|
|
|
|
|
|
| 08 | NDc | Network Detection | ON | when the communications watchdog timer |
|
|
|
|
|
| Signal |
| (period specified by C077) has timed out |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | when the communications watchdog timer is |
|
|
|
|
|
|
|
| satisfied by regular communications activity |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|