Using Intelligent Input Terminals
It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency.
Option | Terminal | Function Name | Input |
|
|
| Description | ||||||||
Code | Symbol | State |
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
27 | UP | Remote Control | ON | Accelerates (increases output frequency) motor | |||||||||||
|
| UP Function (motor- |
| from current frequency | |||||||||||
|
| ized speed pot.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | Output to motor operates normally | ||||||||||||
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
28 | DWN | Remote Control | ON | Decelerates (decreases output frequency) motor | |||||||||||
|
| DOWN Function |
| from current frequency | |||||||||||
|
| (motorized speed |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | Output to motor operates normally | ||||||||||||
|
| pot.) | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
29 | UDC | Remote Control Data | ON | Clears the Up/down frequency memory | |||||||||||
|
| Clear |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | No effect on Up/down memory | ||||||||||||
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C001, C002, C003, C004, | Example (requires input configuration— | |||||||||||||
|
| C005, C006 |
| see page | |||||||||||
Required settings: | A001 = 02 |
|
|
|
| DWN UP | |||||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
| L | 6 | 5 | 4 | 3 | 2 | 1 | PCS |
| ||
Notes: |
|
|
| ||||||||||||
• This feature is available only when the frequency |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
command source is programmed for operator |
|
|
|
|
|
|
|
|
|
|
|
| |||
control. Confirm A001 is set to 02. |
|
|
|
|
|
|
|
|
|
|
|
|
|
• This function is not available when [JG] is in use.
•The range of output frequency is 0 Hz to the value
in A004 (maximum frequency setting). | See I/O specs on page |
|
•The minimum ON time of [UP] and [DWN] is 50 ms.
•This setting modifies the inverter speed from using F001 output frequency setting as a starting point.
Operations and Monitoring