Troubleshooting Flowcharts | Section | |
|
|
|
Power Supply Check |
|
|
PWR indicator not lit.
Is power being | No | ||
supplied? |
|
| |
| Yes |
|
|
|
|
| |
|
| No | |
|
|
|
|
Connect power supply.
Is PWR indicator lit? | Yes |
|
Is voltage adequate?
Yes
No
No
Set supply voltage within acceptable limits.
Is PWR indicator lit? | Yes |
|
Are there any loose | Yes | ||
terminal screws or bro- |
|
| |
|
| ||
ken wires? |
|
| |
| No | No | |
| |||
|
| ||
|
|
|
|
|
|
|
|
Tighten screws or replace wires.
Is PWR indicator lit?
Yes
Has the external | Yes | |
power supply shorted | ||
|
Correct the short circuit or limit the connected load to the spec-
or overloaded? |
(see note) |
No |
No |
Replace the CPU
Unit.
ification range
Is PWR indicator lit?
Yes
End
Note The PWR indicator will go out when there is a short circuit in the external power supply or an overload, only in the
118