Troubleshooting Flowcharts

Section 5-6

 

 

 

Power Supply Check

 

 

PWR indicator not lit.

Is power being

No

supplied?

 

 

 

Yes

 

 

 

 

 

 

 

No

 

 

 

 

Connect power supply.

Is PWR indicator lit?

Yes

 

Is voltage adequate?

Yes

No

No

Set supply voltage within acceptable limits.

Is PWR indicator lit?

Yes

 

Are there any loose

Yes

terminal screws or bro-

 

 

 

 

ken wires?

 

 

 

No

No

 

 

 

 

 

 

 

 

 

 

 

Tighten screws or replace wires.

Is PWR indicator lit?

Yes

Has the external

Yes

power supply shorted

 

Correct the short circuit or limit the connected load to the spec-

or overloaded?

(see note)

No

No

Replace the CPU

Unit.

ification range

Is PWR indicator lit?

Yes

End

Note The PWR indicator will go out when there is a short circuit in the external power supply or an overload, only in the CPM1A-10CDR-jand CPM1A-20CDR-jCPU Units. In CPM1A-30CDR-jand CPM1A-40CDR-jCPU Units, when there is a short circuit or a overload, the external power supply voltage will drop but the PWR indicator will remain lit.