Troubleshooting Flowcharts

Section 5-6

 

 

 

No

Are the IR 00002 and IR 00003 input indi-

A cators operating normally?

From

previousYes page

Check the voltage at

the IR 00002 and IR

00003 terminals.

No

Operation

O.K.?

Yes

No Yes

Check operation by using a dummy input signal to turn the

input ON and OFF.

Check the voltage at the IR 00002 and IR

00003 terminals.

Operation

O.K.?

No

Is input wiring

correct?

No

Wire correctly.

Are the terminal

screws loose?

Yes

No

Yes

Tighten the terminal

screws

 

No

 

Operation

 

 

 

 

O.K.?

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Replace the CPU

 

Check input devices

Unit or Expansion

 

 

LS1 and LS2.

I/O Unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the CPU

Return to “start.”

Unit or Expansion

 

 

 

 

I/O Unit.

122

Page 133
Image 133
Omron CPM1A operation manual 122