Wiring and Connections

Section 3-4

 

 

 

Floor Ducts

Leave at least 200 mm between the wiring and the top of the duct, as shown in the following diagram.

CPM1A I/O lines

Control cables and

Metal plate (iron)

CPM1A power lines

Power cables

200 mm min.

Conduits

Separate the CPM1A I/O lines, power and control lines, and power cables, as shown in the following diagram.

Control cables and

CPM1A I/O lines CPM1A power lines Power cables

3-4-2 Ground Wiring

Grounding

Be sure to ground the earth terminal to less than 100 Ω in order to protect against

 

electric shock and incorrect operation from electrical noise. Be sure to use a wire

 

of at least 1.25 mm2 for grounding.

!WARNING During installation, be sure to ground to 100 Ω max in order to protect against electric shock.

Ground to 100 Ω max.

AC power supply unit

100 to 240 VAC L1

L2/N

COM

01

 

 

00

02

 

 

0 CH

 

Ground to 100 Ω max.

DC power supply unit

24 VDC +

–

COM

01

 

NC

00

02

 

 

0 CH

 

Note The NC terminal is not used.