Wiring and Connections

Section 3-4

 

 

 

3-4-10 CompoBus/S I/O Link Connections

A CompoBus/S I/O Link can be used to create an I/O link (remote I/O) of 8 input points and 8 output points with a CompoBus/S Master Unit or SRM1 PC. The connection is made through a CompoBus/S I/O Link Unit.

From the standpoint of the CPM1A CPU Unit, the area allocated to the Compo-

Bus/S I/O Link Unit can be treated just like the area allocated to an Expansion I/O

Unit. The difference is that the bits are not actual I/O points, but I/O bits in the

Master Unit.

CompoBus/S Master Unit (or SRM1 PC)

CPM1A CPU Unit

CompoBus/S I/O Link Unit

C200HX/HG/HE PC

 

(Slave)

 

 

Cables

Use special flat cable or VCTF cable to connect the nodes in the CompoBus/S I/O Link. (Special flat cables and VCTF cables cannot be combined in the same system.)

Name

Specifications

Flat cable

4-core flat cable, 0.75 mm2

VCTF cable

2-core x 0.75 mm2

65