Selecting an Installation SiteSection 3-2
Note Provide proper shielding when installing in the following locations:
•Locations subject to static electricity or other sources of noise.
•Locations subject to strong electromagnetic fields.
•Locations subject to possible exposure to radiation.
•Locations near to power supply lines.
3-2-2 Panel/Cabinet Installation
| Consider PC operation, maintenance, and surrounding conditions when instal- |
| ling the CPM1A in a panel or cabinet. |
Overheating | The operating temperature range for the CPM1A is 0_C to 55_C. Be sure that |
| there is adequate ventilation for cooling. |
| • Allow enough space for air circulation. |
| • Do not install the CPM1A above equipment that generates a large amount of |
| heat, such as heaters, transformers, or large resistors. |
| • Install a cooling fan or system when the ambient temperature exceeds 55_C. |
| Control panel |
| Fan |
CPM1A
Air vent
Electrical NoisePower lines and
•Do not install the CPM1A in a panel or cabinet with
•Allow at least 200 mm between the CPM1A and nearby power lines.
200 mm min.
CPM1A
200 mm min.
AccessibilityEnsure that the CPM1A can be accessed for normal operation and mainte- nance.
•Provide a clear path to the CPM1A for operation and maintenance.
•The PC will be easiest to access if the panel or cabinet is installed about 3 to 5 feet off of the floor.
38