System Configuration

Section 1-2

 

 

 

1-2-5 One-to-one NT Link Communications

Using the NT Link, the CPM1A PC can connected to the Programmable Termi- nal (NT Link Interface) through an RS-232C Adapter.

OMRON Programmable Terminal

RS-232C

CPM1A CPU Unit

Adapter

RS-232C Cable

WX2Z-200T (2 m)

WX2Z-500T (5 m)

Name

Usage

Model number

 

 

 

RS-232C Adapter

Converts to peripheral port-level

CPM1-CIF01

 

communications.

 

1-2-6 CompoBus/S I/O Link Connections

A CompoBus/S I/O Link can be used to create an I/O link (remote I/O) of 8 input points and 8 output points with a CompoBus/S Master Unit or SRM1 PC. The connection is made through a CompoBus/S I/O Link Unit.

From the standpoint of the CPM1A CPU Unit, the area allocated to the Compo-

Bus/S I/O Link Unit can be treated just like the area allocated to an Expansion I/O

Unit. The difference is that the bits are not actual I/O points, but I/O bits in the

Master Unit.

CompoBus/S Master Unit (or SRM1 PC)

SYSMAC CS1-series PC

CPM1A CPU Unit

CompoBus/S I/O Link Unit

 

(Slave)

Cables

Use special flat cable or VCTF cable to connect the nodes in the CompoBus/S I/O Link. (Special flat cables and VCTF cables cannot be combined in the same system.)

Name

Specifications

 

 

Flat cable

4-core flat cable, 0.75 mm2

VCTF cable

2-core x 0.75 mm2

1-2-7 Peripheral Device Connections

CPM1A programs can be created or edited with a Programming Console or a personal computer running SYSMAC Support Software (SSS).

15

Page 29
Image 29
Omron CPM1A One-to-one NT Link Communications, CompoBus/S I/O Link Connections, Peripheral Device Connections, Cables