Unit Components

Section 2-2

 

 

 

2.DIP Switch

Sets the temperature unit (° C or ° F), and the number of decimal places used.

ON

12

Number of decimal places used

OFF: Normal (0 or 1); ON: 2

Temperature unit

OFF: ° C; ON: ° F

3.Rotary Switch

Sets the temperature range. Set the range in accordance with the specifica- tions of the temperature sensor used.

CPM1A-TS001/002

Set value

Thermocouple

Range (° C)

Range (° F)

 

 

 

 

0

K

–200 to 1,300

–300 to 2,300

 

 

 

 

1

 

0.0 to 500.0

0.0 to 900.0

 

 

 

 

2

J

–100 to 850

–100 to 1,500

 

 

 

 

3

 

0.0 to 400.0

0.0 to 750.0

 

 

 

 

4 to F

---

Setting not possible

 

CPM1A-TS101/102

Set value

Platinum resistance

Range (° C)

Range (° F)

 

thermometer

 

 

 

 

 

 

0

Pt100

–200.0 to 650.0

–300.0 to 1,200.0

 

 

 

 

1

JPt100

–200.0 to 650.0

–300.0 to 1,200.0

 

 

 

 

2 to F

---

Setting not possible

 

4.Expansion I/O Connecting Cable

Connects the Temperature Sensor Unit to the expansion connector on the PC’s CPU Unit, an Expansion I/O Unit, or another Expansion Unit. The cable is connected to the Temperature Sensor Unit and cannot be removed.

!Caution Do not touch the expansion I/O connecting cable while the power is being sup- plied in order to prevent any malfunction due to static electricity.

5.Expansion Connector

Connects to an additional Expansion I/O Unit or another Expansion Unit.

32