95
3. Press the CLR Key or the SHIFT and TR Keys to end the unsigned decimal
display and return to normal monitoring.
CLR c200 cL0020000
FFF0 0000^ OFF
4-3-17 Three-word Data Modification
This operation is used to change the contents of one or more of the 3 con-
secutive words displayed in the Three-word Monitor operation. It is possible
in MONITOR or PROGRAM mode only.
RUN MONITOR PROGRAM
No OK OK
Caution Before changing the contents of I/O memory, be sure that the changes will not
cause equipment to operate unexpectedly or dangerously. In particular, take
care when changing the status of output bits. The PC continues to refresh I/O
bits even if the PC is in PROGRAM mode, so devices connected to output points
on the CPU Unit or Expansion I/O Units may operate unexpectedly.
1, 2, 3... 1. Monitor the status of the desired words according to the procedure
described 4-3-14 Three-word Monitor.
(Three-word monitor)
D0002D0001D0000
0123 4567 89AB
2. Press the CHG Key to begin 3-word data modification. The cursor will
appear next to the contents of the leftmost word.
CHG D0002 3CH CHG?
00123 4567 89AB
3. Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
(Input the new value and press the WRITE Key to write the changes in
memory if no more changes will be made.)
B1CHG D0002 3CH CHG?
0001 4567 89AB
4. Input the new value for the middle word on the display and press the CHG
Key if the rightmost word will be changed. Input the new value and press the
WRITE Key to write the changes in memory if the rightmost word will not be
changed. (In this case, it will not.)
C2D3E4WRITE D0002D0001D0000
0001 0234 89AB
Note If the CLR Key is pressed before the WRITE Key, the operation will be cancelled
and the 3-word monitor display will return without any changes in data memory.
4-3-18 Changing Timer, Counter SV
There are two operations that can be used to change the SV of a timer or
counter. They are possible in MONITOR or PROGRAM mode only. In MON-
ITOR mode, the SV can be changed while the program is being executed.
RUN MONITOR PROGRAM
No OK OK
The timer or counter SV can be changed either by inputting a new value or
by incrementing or decrementing the current SV.
Programming Console Operations Section 4-3