Maintenance Inspections

 

 

 

Section 5-7

 

 

 

 

 

 

 

5-7

Maintenance Inspections

 

 

 

 

 

 

 

 

 

In order that your SYSMAC system operates in optimum condition, be sure to

 

 

 

 

carry out daily or periodical inspections.

 

 

 

Inspection Items

 

 

The main system components of a SYSMAC system are semiconductors, and it

 

 

 

 

contains few components with limited lifetimes. Environmental conditions, how-

 

 

 

 

ever, can lead to electrical element deterioration, making regular maintenance

 

 

 

 

necessary.

 

 

 

 

 

 

 

 

 

The standard period for maintenance checks is 6 months to 1 year, but depend-

 

 

 

 

ing on the environment checks may need to be more regular.

 

 

 

 

If the criteria are not met, adjust to within the specified ranges.

 

 

 

 

 

 

 

 

 

 

Inspection items

 

 

Details

Criteria

Remarks

 

 

 

 

 

 

 

 

Power supply

 

Determine whether the

Within the voltage variation

Tester

 

 

 

voltage fluctuation is within

range (see note)

 

 

 

 

 

 

the standard at the power

 

 

 

 

 

 

 

 

supply terminal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Environmental conditions

 

Is the ambient temperature

0 to 55_C

 

Thermometer

 

 

 

inside the panel

 

 

 

 

 

 

 

 

appropriate?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the ambient humidity

10% to 90% RH with no

Hydroscope

 

 

 

inside the panel

condensation

 

 

 

 

 

 

appropriate?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Has dirt or dust collected?

None

 

Visual inspection

 

 

 

 

 

 

 

 

I/O power supply

 

Is the voltage fluctuation

Each I/O must conform to

Tester

 

 

 

measured at the I/O

the specifications

 

 

 

 

 

 

terminal within the standard

 

 

 

 

 

 

 

 

range?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation status

 

Are all units securely

Nothing is loose

 

Positive screwdriver

 

 

 

installed?

 

 

 

 

 

 

 

 

Are all connection cables

Nothing is loose

 

Visual inspection

 

 

 

and connectors inserted

 

 

 

 

 

 

 

 

completely and locked?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are any of the external

Nothing is loose

 

Positive screwdriver

 

 

 

wiring screws loose?

 

 

 

 

 

 

 

 

Are any of the external

No external abnormalities

Visual inspection

 

 

 

wiring cables frayed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product service life

 

Contact output relay

Electrical:

 

 

 

 

 

 

 

 

Resistance load: 300,000

 

 

 

 

 

 

 

operations

 

 

 

 

 

 

 

 

Inductive load: 100,000

 

 

 

 

 

 

 

operations

 

 

 

 

 

 

 

 

Mechanical:

 

 

 

 

 

 

 

 

10,000,000 operations

 

 

 

 

Note Power supply voltage variation range.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

Allowable voltage fluctuation range

 

 

 

 

 

 

 

 

 

 

 

 

 

100 to 120 VAC

 

 

85 to 132 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

200 to 240 VAC

 

 

170 to 264 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VDC

 

 

20.4 to 26.4 VDC

125

Page 136
Image 136