Using a Programming Console | Section | |
|
|
|
Startup Operating Mode The operating mode of the CPM1A when the power is turned ON depends upon the PC Setup setting in DM 6600 and the Programming Console’s mode switch setting if the Programming Console is connected.
PC Setup setting | Programming | Programming Console not |
(DM 6600) | Console connected | connected |
|
|
|
0000 | The startup mode | RUN mode if no Programming Device |
| determined by the | is connected. PROGRAM mode if |
| mode switch setting. | another Programming Device is |
|
| connected. |
|
|
|
0100 | The startup mode is the same as the operating mode before | |
| power was interrupted. |
|
|
|
|
0200 | PROGRAM mode |
|
|
|
|
0201 | MONITOR mode |
|
|
|
|
0202 | RUN mode |
|
Note The default setting is 0000. If a Programming Console is not connected, the PC will automatically enter RUN mode. Be sure that it is safe for the PC to operate before turning on the PC without a Programming Console connected.
4-2-3 Connecting the Programming Console
Connect the Programming Console’s connecting cable to the CPM1A’s periph- eral port, as shown below.
Panel Installation | The | |
| as shown in the following diagram. (The | |
| separately.) |
|
| Mounting Bracket | Mounting hole dimensions |
| (DIN43700 standards) |
Two screws
Panel thickness: 1.0 to 3.2 mm
92
77