Promise Technology M500p, M500i Monitor the Shutdown, Restart the Subsystem, Monitor the Restart

Models: M500i M200f M300f M200p M500p M300p M200i M500f M300i

1 322
Download 322 pages 2.01 Kb
Page 120
Image 120

VTrak M-Class Product Manual

When the controller shuts down, your WebPAM PROe connection will be lost.

8.Wait for no less than two minutes.

9.Manually turn off the power supply switches on the back of the subsystem.

Monitor the Shutdown

To monitor a shutdown, you must use the Command Line Interface (CLI) though a serial connection to the VTrak.

At the “administrator@CLI>” prompt, type shutdown -a shutdown.

When the “Shutdown complete. It is now safe to power off the subsystem.” message appears, turn off the power supply switches.

Restart the Subsystem

1.Click on the Subsystem icon in Tree View.

2.Click on the Administrative Tools icon.

3.Click on the Shutdown link in Management View. A Shutdown or Restart tab will appear.

4.On the Shutdown or Restart tab, select Restart from the dropdown menu.

5.Click the Submit button.

6.In the warning box, click the OK button.

7.In the confirmation box, type the word confirm in the field provided.

8.Click the OK button.

When the controller shuts down, your WebPAM PROe connection will be lost.

9.Wait for two to three minutes.

10.In your browser, log into WebPAM PROe once again.

If you cannot log in, wait for 30 seconds, and try again. Repeat until login is successful.

Monitor the Restart

To monitor a restart, you must use the Command Line Interface (CLI) though a serial connection to the VTrak.

At the “administrator@CLI>” prompt, type shutdown -a restart.

When the “Login:” prompt appears, the restart is finished.

112

Page 120
Image 120
Promise Technology M500p, M500i, M500f, M300p, M300i, M300f Monitor the Shutdown, Restart the Subsystem, Monitor the Restart