Chapter 4: Management with WebPAM PROe
Enclosure
Enclosure Information
The
•SEP Firmware Version
•Polling Interval*
•Enclosure Warning and Critical temperature thresholds*
•Controller Warning and Critical temperature thresholds*
•Power Supply Units – Device ID, Status, Fan status, and Fan speed
•Blowers (scroll fans in the cooling unit(s) – Device ID, Status, and Speed
•Voltage Sensors – 3.3V, 5.0V, and 12.0V
•Temperature Sensors – The number of sensors varies among VTrak models To access Controller information:
1.Click the Subsystem icon in Tree View.
2.Click on the Enclosures icon.
3.Click on the Enclosure icon.
For information on Enclosure problems, see “Chapter 8: Troubleshooting” on page 261.
Enclosure Settings
The
1.Click the Subsystem icon in Tree View.
2.Click on the Enclosures icon.
3.Click on the Enclosure icon.
4.Click on the Settings tab in Management View.
5.Enter a polling interval (15 to 255 seconds) in the Polling Interval field.
6.Enter a value in the Enclosure Warning Temperature Threshold field (45°C is the default).
7.Enter a value in the Enclosure Critical Temperature Threshold field (51°C is the default).
8.Enter a value in the Controller Warning Temperature Threshold field (63°C is the default).
9.Enter a value in the Controller Critical Temperature Threshold field (68°C is the default).
119