Quick Start

Quick Start Wizard via the handheld programmer

Notes:

The wizard is a complete package and the settings are inter-related.

Do not use the Quick Start wizard to modify individual parameters: see instead Parameter Reference on page 43.

Changes apply only at the end of the sequence, after you select Apply changes.

The Quick Start menu appears as soon as you activate PROGRAM mode.

1. Quick Start

Note: There is no need to perform a Reset before starting the Quick Start sequence.

a.Point the programmer at the display (from a maximum distance of 600 mm [2 ft.]), then press Mode to activate PROGRAM mode and open Menu level 1.

b.Press Right ARROW to navigate to menu item 1.1.

c.Press Right ARROW to open Edit mode: the PROGRAM icon will flash.

d.To change a setting, scroll to the desired selection or key in a new value.

e.After modifying a value, press Right ARROW to accept it. The LCD displays the next menu item, the PROGRAM icon disappears, and the rightmost digit

flashes to indicate Navigation Mode.

1.1.Language

Options ENGLISH, DEUTSCH, FRANCAIS, ESPANOL

1.2. Application Type

 

Options

STEEL

Silo construction

 

 

 

 

CONCRETE

 

 

 

 

1.3. Operation

 

 

 

 

 

 

 

 

LEVEL

Distance to material surface referenced from Low Calibration

 

 

Point (process empty level).

 

 

 

 

 

 

 

 

Options

SPACE

Distance to High Calibration Point (process full level)

 

referenced from material surface.

 

 

 

 

 

 

 

 

 

DISTANCE

Distance to material surface referenced from Sensor

 

 

Reference Point.

 

 

 

 

 

 

 

Page 28

SITRANS LR 460 – INSTRUCTION MANUAL

7ML19985JM01

Page 34
Image 34