Quick Start

Level application example

The application is a steel silo containing flour that takes an average 3 hours to fill and 3 weeks to empty.

Using the Easy Aimer, the LR 460 is oriented so that the emission cone is approximately perpendicular to the material surface.

Fill rate = 0.09 m/minute (15.5 / 180). Response rate has been set to slow: 0.1 m/minute, or slightly faster than the fill rate.

LR 460 with Easy Aimer

Sensor Reference Point (flange face)

1.0 m

High Calibration Point

15.5 m

Level

Low Calibration Point

Quick Start Setting

Description

Language

ENGLISH

 

 

 

 

Application Type

STEEL

Silo construction

 

 

 

Operation

LEVEL

Material level referenced from Low Calibration point.

 

 

 

Units

m

 

 

 

 

High Calibration Point

1.0

Process full level.

 

 

 

Low Calibration Point

15.5

Process empty level.

 

 

 

Rate

SLOW

Response rate = 0.1 m/minute.

 

 

 

Apply Changes

YES

Save new settings.

 

 

 