Quick Start
Level application example
The application is a steel silo containing flour that takes an average 3 hours to fill and 3 weeks to empty.
Using the Easy Aimer, the LR 460 is oriented so that the emission cone is approximately perpendicular to the material surface.
Fill rate = 0.09 m/minute (15.5 / 180). Response rate has been set to slow: 0.1 m/minute, or slightly faster than the fill rate.
LR 460 with Easy Aimer
Sensor Reference Point (flange face)
1.0 m
High Calibration Point
15.5 m
Level
Low Calibration Point
Quick Start Setting | Description | |
Language | ENGLISH |
|
|
|
|
Application Type | STEEL | Silo construction |
|
|
|
Operation | LEVEL | Material level referenced from Low Calibration point. |
|
|
|
Units | m |
|
|
|
|
High Calibration Point | 1.0 | Process full level. |
|
|
|
Low Calibration Point | 15.5 | Process empty level. |
|
|
|
Rate | SLOW | Response rate = 0.1 m/minute. |
|
|
|
Apply Changes | YES | Save new settings. |
|
|
|
Page 34 | SITRANS LR 460 – INSTRUCTION MANUAL | 7ML19985JM01 |