Parameters
2. Identification
Operation Unit
Tag
Text that can be used in any way, for example as a unique label for a field device in the plant.
Description
Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use.
Message
Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use..
Note: Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated
2.1.Configuration
2.1.2.Address
The unique address of the device on the network (PROFIBUS or HART address).
Values | PROFIBUS PA | 0 - 126, default: 126 (We recommend a setting in the range | |
1 to 125.) | |||
| |||
| HART | 0 to 15,default: 0 | |
|
|
|
To set the address via the handheld programmer:
•Press Mode to activate PROGRAM mode, menu item 1.0.
•Press Down ARROW , Right ARROW , Right ARROW to navigate to Address.
•Press Right ARROW to open Edit mode: the PROGRAM icon will flash.
•If required, key in a new value and press Right ARROW to accept it.
To set Address via PDM (PROFIBUS PA only):
Open the menu Device – Set Address.
2.1.3. Remote operation enable (REMLOCK)
Enables or disables programming via the network and PDM.
Handheld programmer | 0 | * | Remote operation enabled |
Values |
|
|
|
1 |
| Remote operation disabled | |
|
|
|
|
Page 46 | SITRANS LR 460 – INSTRUCTION MANUAL | 7ML19985JM01 |