3.5.6.3. TVT Hover Level
Defines in percent how high the TVT (Time Varying Threshold) curve is placed above the echo profile, with respect to largest echo.
Values
Range: 0 to 100%
Default: 40%
3.5.6.4. Manual TVT Shaper Mode
Enables the TVT curve to be manually adjusted at a specified range.
Options |
| ON | |
|
| ||
* | OFF | ||
| |||
|
|
|
3.5.7. Manual TVT shaper
You can manually adjust the TVT curve by entering values for up to 120 breakpoints on the curve.
Values | Range: | ||
|
| ||
Preset: 0 | |||
| |||
|
|
| |
Related | • | 3.5.6.4. Manual TVT Shaper Mode | |
|
|
|
Use this feature to bias the shape of the TVT curve to avoid selecting false echoes from fixed objects.
Each breakpoint is normalized to a value of 0. Change the value of the breakpoints to adjust the curve. In the case of multiple false echoes, shaping can be applied along different points of the curve. Shaping should be applied sparingly in order to avoid missing the true echo.
The Manual TVT shaper feature allows you to adjust the TVT curve while viewing the echo profile.
To change a breakpoint via PDM:
a.Confirm that Shaper Mode is selected.
b.Open the menu Device – TVT Shaper then either adjust the curve manually, or enter values for the desired breakpoints. (See Manual TVT Shaper on page 38.)
To change a breakpoint via the handheld programmer:
a.Confirm that Shaper Mode is selected.
b.Access the submenu for the breakpoint number in question and enter values for all desired breakpoints.
3.5.7.1.Shaper A (1 - 9).
3.5.7.2.Shaper B (10 - 18)
3.5.7.3.Shaper C (19 - 27)
Parameters
7ML19985JM01 | SITRANS LR 460 – INSTRUCTION MANUAL | Page 59 |