B: Troubleshooting

Troubleshooting LR 460 (cont’d)

Symptom

Possible cause

Remedy

 

 

 

 

 

Increase TVT manually at vessel bottom

Reads empty

Reads vessel bottom

region.

when vessel not

through low dK material.

Set Far Range to a lower value.

empty.

 

Lower TVT hover level.

 

 

 

Reading

Due to solids’ sloped

Reduce response rate.

surfaces some fluctuation

Decrease fill/empty parameter values.

fluctuates.

is normal.

Increase filter time constant in AIFB.

 

 

 

 

Echo has double

 

Increase Echo Reform.

peak/is split

 

 

 

 

 

 

Reading is too

 

Increase response rate.

 

Turn off Window tracking.

slow and lags

 

 

Change fill/empty rate parameter

behind actual

 

 

values.

level change.

 

 

Increase filter time constant in AIFB.

 

 

 

 

 

Device cannot

 

Make sure local operation is enabled.

be programmed

 

See Local Operation Enable on page 49.

via the

 

Also make sure that Write Locking is

handheld

 

Off. See Write Locking on page 49.

programmer

 

 

 

 

 

You are unable

 

Make sure remote operation is

 

enabled. See Remote operation enable

to modify a

 

 

(REMLOCK) on page 46. Also make sure

parameter via

 

 

that Write Locking is Off. See Write

remote

 

 

Locking on page 49.

communications

 

 

 

 

 

 

Page B-78