F; Profile structure HART

Appendix F: HART Information Structure

SITRANS LR 460 detects a material level via the sensor, and then processes that information to provide a measured value. The measured value is conveyed as a digital signal.

The LR 460 device design enables it to provide outputs to two different channels:

a 4-20 mA channel

a digital channel

Block Model for recording and processing measured values

The LR 460 follows a profile block model similar to a PROFIBUS Profile 3.01, Class B, PA device. The functions of the device are divided into blocks.

Information is recorded by the sensor, then passed through the Level Transducer Block to two independent Analog Input Function Blocks (AIFB1 and AIFB2).

The parameters used to configure the Function Blocks are standard profile parameters, following a convention similar to that used in the PROFIBUS Profile Structure. They can be modified by HART communications via PDM.

 

sensor

 

 

 

 

 

 

Analog

 

 

electronics

 

Input

 

 

temperature

 

Function

 

 

 

PV

Block 1

HART

 

Level

 

 

SV1

 

sensor

 

PV

Transducer

Analog

 

 

 

Block

SV2

Input

 

 

 

 

Function

 

 

 

 

Block 2

HART

 

 

 

 

SV

 

 

 

 

HART

 

 

 

 

Digital

 

 

 

 

Channel

mA Output Block

4-20 mA Channel

Level Transducer Block (LTB)

The Level Transducer Block carries out adjustments to the sensor, such as level calibration. It supplies the output (Primary Value/PV, or Secondary Value 1/SV!, or Secondary Value 2/SV2) which is utilized by either or both of the AIFBs.

Page F-90

SITRANS LR 460 (HART) – INSTRUCTION MANUAL

7ML19985JM01

Page 96
Image 96
Siemens LR 460 instruction manual Block Model for recording and processing measured values, Profile structure Hart, F-90