Siemens LR 460 instruction manual Interface

Models: LR 460

1 123
Download 123 pages 8.81 Kb
Page 13
Image 13

Long-term stability

≤ ± 1 mm/year

Near Range (blanking)

0.35 m (1.15 ft)

Update time

mA output and loop display is updated once per

 

 

second

Beam angle

 

3" horn:

11° at –3 dB boundary

4" horn:

8° at –3 dB boundary

Memory

non-volatile EEPROM

no battery required

Interface

Analog output (Not applicable to PROFIBUS PA option)

signal range

4 to 20 mA

 

 

upper limit 20 to 23 mA adjustable

fail signal

3.6 mA to 23 mA; or last value

load

Max. 600 ; for HART1 communication min. 230

Digital output

 

function

Configurable as a device status or limit value (level)

signal type

Relay, either NCC or NOC function, max. 50 V DC,

 

 

max. 200 mA, rating max. 5 W.

 

 

Self-resetting fuse, Ri = 9

Electrical isolation

Outputs electrically isolated from the power supply and

 

 

from each other

Display

 

LCD

two lines of 16 characters each, configurable for the

 

 

following displays:

 

 

level, amplitude, digital output,

 

 

temperature, validity, signal-to-noise ratio,

 

 

output current, distance

Specifications

1.HART® is a registered trademark of HART Communication Foundation.

7ML19985JM01

SITRANS LR 460 – INSTRUCTION MANUAL

Page 7