Quick Start

Quick Start

Note: SITRANS LR 460 only supports SIMATIC PDM version 6.0 with SP2.

To set up SITRANS LR 460 for a simple application requires only the following settings:

select application type (silo construction)

select operation mode: level, distance or space

set speed of response

set High and Low Calibration Points

A Quick Start wizard groups together all the settings you need. There are two ways to access the wizard:

Quick Start Wizard via the handheld programmer on page 28

Quick Start Wizard via SIMATIC PDM on page 30

Activating SITRANS LR 460

Notes:

Keep infrared devices such as laptops, cell phones, and PDAs, away from SITRANS LR 460 to prevent inadvertent operation.

Frequently switching the device off and on causes wear of the electronics (see 2.3. Statistics on page 49 to access the records).

Power up the instrument. SITRANS LR 460 automatically starts up in RUN mode, and detects the distance to the material level referenced from the sensor flange face. The LCD displays the measurement and the default unit is meters. System status is displayed on the LCD, or on a remote communications terminal.

RUN mode display

 

Normal operation

 

level

reliable echo

indicator1

units

flashing

 

98.82 m

heartbeat2

3.800 mA

 

mA value, HART only (press key 5 on

handheld programmer to activate)

LOE condition

unreliable echo indicator1

98.82 m

S:0

fault code

See RUN mode (startup display) on page 85 for more detailed information.

1.See Loss of Echo (LOE) on page 74 for more detail.

2.Flashes once per second to indicate that the device is functioning.

Page 26

SITRANS LR 460 – INSTRUCTION MANUAL

7ML19985JM01

Page 32
Image 32
Siemens LR 460 instruction manual Quick Start, Activating Sitrans LR, RUN mode display