3. Input

Static Revision Number

The revision level of the static data associated with the Level Transducer Block, updated whenever a standard profile configuration parameter is changed.

Class

Indicates the Level Transducer Block as per PROFIBUS PA Profile specifications.

3.2.Standard Setup

3.2.1.Antenna

Identifies antenna configuration.

Options

3" HORN 4" HORN

3.2.2. Response Rate

Sets the reaction speed of the device to measurement changes in the target range.

Related

Response

LOE Timer1

Fill Rate

Empty Rate

parameters

Rate

 

(minutes)

 

 

 

 

 

 

 

 

 

 

 

*

 

SLOW

100

0.1 m/minute

0.1 m/minute

Values

 

 

 

 

 

 

 

 

MED

10

1 m/minute

1 m/minute

 

 

 

 

 

 

 

 

 

 

FAST

1

10 m/minute

10 m/minute

 

 

 

 

 

 

 

Note: If you change Response Rate it resets the following parameters: LOE

Timer, Fill Rate, and Empty Rate.

Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy and a smoother output signal: faster settings allow for more level fluctuation.

Parameters

1.For instructions on usage see 3.5.1.1. LOE (Loss of Echo) Timer . For technical details see LOE Timer .

Page 50

SITRANS LR 460 – INSTRUCTION MANUAL

7ML19985JM01

Page 56
Image 56
Siemens LR 460 instruction manual Input