Siemens LR 460 Calibration via Simatic PDM, Configuring Profibus PA with an S7-300/ 400 PLC

Models: LR 460

1 123
Download 123 pages 8.81 Kb
Page 100
Image 100

G: Remote Operation PA

Configuring PROFIBUS PA with an S7-300/ 400 PLC

1.If SITRANS LR 460 is not listed in the STEP 7 device catalog, you can download the DeviceInstall file from the Siemens Milltronics Web site and run it from your computer. Go to https://pia.khe.siemens.com/index.asp?Nr=14655 and click Downloads.

2.Add the SITRANS LR 460 "rack": click and drag the SITRANS LR 460 folder from the hardware catalog.

3.Fill the rack with desired modules, by dragging and dropping them from the hardware catalog.

4.After configuring PROFIBUS PA in steps 2 and 3, download it to the PLC.

5.Add code to the PLC program to read data consistently using the SFC14.

Calibration via SIMATIC PDM

1.Open the menu Device – Sensor Calibration and select the button Dry Calibration.

2.Enter the new value for Low Calibration Point (default units are meters). Click OK.

3.Enter the corresponding value for Low Level Point in percent (default is 0). Click OK.

4.Enter the new value for High Calibration Point (default units are meters). Click OK.

5.Enter the corresponding value for High Level Point in percent (default is 100). Click OK.

6.The message ’Sensor Trim Successful’ appears. Click OK.

7.SITRANS LR 460 is now ready to operate.

For a complete list of parameters, see Parameter Reference on page 43.