Note: Primary Value (PV) is the default measured value; Secondary Value 1 (SV1) is an equivalent value.

The figure below shows the signal flow of measured values from the sensor through the Level Transducer Block into the output value (Primary Value/ Level; Secondary Value 1 / Level; or Secondary Value 2 /Distance. The LTB implements all of the basic parameters

(see parameter diagram on page 101).1

Level Transducer Block

 

 

 

 

Primary Value

 

 

 

Sensor Value

Level

Level

 

 

 

(sensor units)

(level units)

(level units)

 

 

Sensor

Sensor

Level

 

Linearization

PV

 

technology

calibration

 

 

 

(turned off)1

 

 

 

 

 

 

 

 

 

 

 

Level

 

 

AIFB1

 

 

 

Offset

Linearization

 

(Analog

 

Sensor

High

Low

Type

SV1

Input)

 

Offset

Calibration

Calibration

Secondary Value 1

 

 

 

Point

Point

 

 

 

 

 

 

 

 

High Level

Low Level

[Level]

 

 

 

 

Point

Point

(Level Units)

 

AIFB2

 

 

Calibration

 

 

 

 

 

SV2

(Analog

 

 

Type

 

Input)

 

 

 

 

 

 

 

 

Secondary Value 2

 

 

 

 

 

 

[Distance]

 

 

 

 

 

 

(Sensor Units)

 

 

How the Level Transducer Block works:

1.The sensor technology block selects the proper echo. See Echo selection on page 72 for more detail.

The sensor value (in sensor units) is checked to see if it is within its measuring limits. If the limit is exceeded, this results in a Bad status and the error message Failure in measurement. The sensor value is stored in Sensor Value.

The analog signal from the sensor is transformed into a digital signal.

A Sensor Offset (default 0) provides compensation if necessary for differences between the vessel reference point and the sensor reference point.

1.A Linearization module is required by the PROFIBUS PA specifications. The Linearization block is turned off in SITRANS LR 460.