Parameters
3.5.7.4.Shaper D (28 - 36)
3.5.7.5.Shaper E (37 - 45)
3.5.7.6.Shaper F (46 - 54)
3.5.7.7.Shaper G (55 - 63)
3.5.7.8.Shaper H (64 - 72)
3.5.7.9.Shaper I (73 - 81) 3.5.7.A. Shaper J (82 - 90) 3.5.7.B. Shaper K (91 - 99)
3.5.7.C. Shaper L (100 - 108) 3.5.7.D. Shaper M (109 - 118) 3.5.7.E. Shaper N (119 - 120)
3.5.8.Rate
3.5.8.1.Fill Rate
Defines the maximum rate at which the reported sensor value is allowed to increase.Allows you to further adjust the LR 460 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered.
Values | Range: 0.0000 to 99999 m / min. | |
| ||
Default: 10.000 | ||
| ||
Altered by | Response Rate | |
Related | Unit (Level) | |
| High Level Point | |
|
|
Enter a value slightly greater than the maximum
3.5.8.2. Empty rate
Defines the maximum rate at which the reported sensor value is allowed to decrease.Adjusts the LR 460 response to decreases in the actual material level. Empty Rate is automatically updated whenever Response Rate is altered.
Values | Range: 0.0000 to 99999 m / min. | |
| ||
Default: 10.000 | ||
| ||
|
| |
Altered by | Response Rate | |
|
| |
Related | Units (Level) | |
| High Level Point | |
|
|
Enter a value slightly greater than the vessel’s maximum emptying rate, in Sensor Units per minute.
Page 60 | SITRANS LR 460 – INSTRUCTION MANUAL | 7ML19985JM01 |