B: Troubleshooting

LCD

 

Meaning (cont’d)

Corrective Action

Byte

Bit

display

 

(cont’d)

 

 

Calibration interval as

 

 

 

S: 17

 

defined in Maintenance

Perform calibration.

 

1

 

 

Required Limit has expired.

 

 

 

 

 

 

 

2

 

 

 

Calibration interval as

 

 

 

 

 

 

 

S: 18

 

defined in Maintenance

Perform calibration.

 

2

 

 

Demanded Limit has expired.

 

 

 

 

 

 

 

 

 

 

 

Internal device failure caused

Repair required: contact your

 

 

S:28

 

local Siemens

 

4

 

 

by a memory error.

representative.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair required: contact your

 

 

S:29

 

EEPROM damaged.

local Siemens

 

5

 

 

 

representative.

3

 

 

 

 

 

 

 

 

 

Reset power. If error persists,

 

 

 

 

 

 

S:30

 

EEPROM corrupt.

contact your local Siemens

 

6

 

 

 

representative.

 

 

 

 

 

 

 

 

 

 

 

Repair required: contact your

 

 

S:31

 

Flash error.

local Siemens

 

7

 

 

 

representative.

 

 

 

 

 

 

 

 

 

 

 

Ensure value of the Ident

 

 

 

 

The IDENT number used in

number selector is correct

 

 

S: 32

 

communications, and number

for the network

 

0

 

selected by the Ident Number

configuration. If it is correct,

 

 

 

 

 

 

 

Selector do not correspond.

the device needs to be re-

4

 

 

 

 

parameterized by the PLC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory calibration for the

Repair required: contact your

 

 

S:33

 

internal temperature sensor

local Siemens

 

1

 

 

has been lost.

representative.

 

 

 

 

 

 

 

 

Page B-82