Siemens LR 460 instruction manual Hart wiring, AC version DC version

Models: LR 460

1 123
Download 123 pages 8.81 Kb
Page 26
Image 26

mmmmm Wirng

HART wiring

Note: LR 460 HART requires no power from the 4-20 mA loop.

Install in accordance with Wiring and Installation in the HART Application Guide (order number HCF_LIT-34), available from: http://www.hartcomm.org/technical/doclist.html.

AC version

 

DC version

 

cable clamp

earth

cable clamp

earth

 

terminal

 

terminal

3

4

5

6

7

 

8

 

1

2

3

4

5

6

7

 

8

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated temperature of

L1

L2

 

 

 

 

 

 

 

 

Rated temperature of

 

 

 

 

 

 

 

 

mA

 

connection cables must

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exceed maximum ambient

 

 

 

 

 

mA

 

connection cables must

19-30 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature by at least 15 K

 

 

 

 

 

 

 

exceed maximum ambient

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature by at least 15 K

Connecting HART

Typical PLC/mA configuration with HART

Notes:

For error-free communication via the HART protocol, a 250 Ohm resistor may be required if the loop resistance is less than 250 Ohms.

Only one HART communication device should be inserted in the loop.

LR 460

PLC with mA input card

R = 250

PC/laptop with HART modem running PDM

HART Communicator 375

3.Connect the earth conductor of the power supply to the earth terminal on the metal bracket inside the enclosure. Adjust the cable length so that the earth conductor would be last to disconnect if cable is pulled.

Page 20

SITRANS LR 460 – INSTRUCTION MANUAL

7ML19985JM01