Parameters
4.1.8.5. Limit Hysteresis
Hysteresis is used to adjust the sensitivity of the trigger for alarm messages. It is used to compensate when a process variable fluctuates around the same value as a limit. A high level alarm occurs when a value exceeds an upper limit. The alarm’s status remains true until the value drops below the limit minus the alarm hysteresis. The directions are reversed for low limit detection.
Enter a value for the hysteresis here, to be used for all warnings and alarms. The units are the same as the output value scale.
4.1.8.6. Min Out
Min Out is a minimum peak indicator for the AIFB output values.
4.1.8.7. Max Out
Max Out is a maximum peak indicator for the AIFB output values.
4.1.9.Fail-safe Mode (PROFIBUS PA only)
4.1.9.1.
Handheld |
|
|
programmer |
| Material level to be reported |
Options |
|
|
FS VALUE |
| Default value used as output value. |
|
|
|
LAST VAL | * | Store last valid output value. |
|
|
|
USE BAD |
| Calculated output value is incorrect. |
|
|
|
4.1.9.2. Fail-safe Value
(Accessible in PDM only after FS VALUE is selected in
Values | Range: | |
| ||
Default: 0.000 | ||
| ||
|
|
4.1.A. Human Interface
4.1.A.1. Decimal Point
The number of digits to display after the decimal point.(The LCD is limited to displaying three decimal places.)
Out unit text
If the code list does not contain a desired unit for the OUT parameter, (see General Requirement) you can write the specific text in this parameter.
Page 64 | SITRANS LR 460 – INSTRUCTION MANUAL | 7ML19985JM01 |