2.1.5. Reset
Notes:
•After resetting to Factory Defaults, complete reprogramming is required.
•Resetting to Factory Defaults does not clear values in the Quick Start Wizard: they can be
•Performing a Device Reset clears all values from the Quick Start Wizard.
Two Reset options are available via SIMATIC PDM. Selecting Factory Default resets all parameters excluding device addresses to default values.Device Reset (Warm Start ) has the same effect as recycling power. Only Factory Default is available via the handheld programmer.
| HART | PROFIBUS | Description | |
Handheld | PARAMS | PARAMS | Factory Defaults | |
|
|
| ||
|
| Device Reset: restarts the device (this | ||
Program- |
| WARMSTART | ||
| option is rarely used). | |||
mer |
|
| ||
|
|
| ||
| ADDRESS | Reset PROFIBUS address to 126. | ||
Options |
| |||
|
|
| ||
NONE | NONE | No reset performed. | ||
| ||||
|
|
|
|
To perform a Reset via the handheld programmer:
a.Press Mode to open PROGRAM mode, and key in 215 for Quick Access, or use ARROW keys to navigate to Reset.
b.Press RIGHT Arrow to open Edit Mode.
c.Press DOWN Arrow to scroll to PARAMS and RIGHT Arrow to select it. After the Reset is performed, the display will return to NONE.
d.Press Mode to return to Measurement Mode.
To perform a Reset via SIMATIC PDM:
Open the menu Device – Reset, and select Factory Defaults or Device Reset (for more detail see Device Reset on page 41).
Reset Fault
Resets the Fault message after an active fault has occurred and been corrected. This is required only for faults listed as requiring a manual reset in the General Fault Code list (see page 80).
Open the menu View – Clear Faults. You will see the fault listed. Click Transfer.
To reset via the handheld programmer, key in the value of the fault code in question.
Parameters
7ML19985JM01 | SITRANS LR 460 – INSTRUCTION MANUAL | Page 47 |