3.5.2.4.Narrow Echo Filter (default 0) Filters out echoes of a specific width.
Values | 0 = OFF | ||
|
| ||
greater = wider | |||
| |||
Related | • | 3.6.2.1. Echo Confidence Long | |
Parameters | • | 3.5.2.5. Reform Echo (default 0) | |
|
|
|
To remove a false echo from the Echo Profile, take its width in mm and multiply it by 0.014. Enter the result.
For example, to filter out a spike with 500 mm width enter 7 (the sum of 500 x 0.014).
When a value is keyed in, the nearest acceptable value is entered. 3.5.2.5. Reform Echo (default 0)
Smooths jagged peaks in the echo profile. Reforms fragmented echoes into one echo.
Values | 0 = OFF | ||
| |||
Greater = Wider | |||
| Recommended range 10 to 20: higher is not recommended. | ||
Related | • | Material | |
Parame- | • | 3.5.2.1. Echo Algorithm | |
• 3.5.2.4. Narrow Echo Filter (default 0) | |||
ters | |||
• | 3.5.2.3. Echo Marker | ||
|
|
|
Use this feature when monitoring solids, if the reported level fluctuates slightly even though the monitored surface is still.
Enter the amount of smoothing required. When a value is keyed in, the nearest acceptable value is entered.
3.5.2.6. Echo detection position
The point on the selected echo from which the measured value is taken.
Options | * | CENTER |
|
| |
| RISING | |
|
| |
|
|
|
3.5.3.Echo Sampling
3.5.3.1.Window.
A "distance window" centered on the echo, used to derive the reading. When a new measurement is in the window, the window is
When the value is 0, the window is automatically calculated after each measurement.
•For slower Measurement Response values, the window is narrow.
•For faster Measurement Response values, the window becomes progressively wider.
Parameters
7ML19985JM01 | SITRANS LR 460 – INSTRUCTION MANUAL | Page 55 |