1.4. Units

Select the units for the Quick Start variables (high and low calibration point, and level, distance, or space).

Options

mm, cm, m, in, ft

1.5. High Calibration Point

Distance from Sensor Reference to High Calibration Point: usually process full level (see illustration to 1.3)

Values

Range: 0.0000 to 100.00 m

1.6. Low Calibration Point

Distance from Sensor Reference to Low Calibration Point: usually process empty level (see illustration to 1.3)

Values

Range: 0.0000 to 100.00 m

1.7. Rate

Sets the reaction speed of the device to measurement changes in the target range.

 

SLOW

0.1 m/minute

Options

 

 

MED

1.0 m/minute

 

 

 

 

FAST

10.0 m/minute

 

 

 

Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy: faster settings allow for more level fluctuation

1.8. Apply Changes

In order to save the settings changed in the Quick Start wizard it is necessary to enable Apply Changes.

Options

YES, NO

Parameters

7ML19985JM01

SITRANS LR 460 – INSTRUCTION MANUAL

Page 45

Page 51
Image 51
Siemens LR 460 instruction manual Slow