4.3.9. 20 mA Trim

Calibrates the 20 mA output.

Values

Range: 18 to 24 mA

Related parame-

4.3.1. Function

A mA value derived from the ratio of current level to the range

ters

between Lower Value and Upper Value.

 

 

 

a.Set 4.3.1. Function to MANUAL mode.

b.Set 4.3.3. Man Value to 20 mA.

c.Attach a calibrated meter and check the output at the terminals. Record the remote reading in mA.

d.Enter the recorded value in 4.3.9. 20 mA Trim .

e.Restore 4.3.1. Function to its previous setting.

f.Confirm that the mA output is as expected.

4.4.Relay Configuration

4.4.1. AIFB

Select AIFB1 or AIFB2. 4.4.2. Function

Handheld programmer Options

DISABLED

*

MANUAL

 

LO ALM

 

HI ALM

 

ANY ALM

 

FAIL-SAFE

 

4.4.3. NC/NO

 

Handheld programmer

NO

*

Normally Open

 

options

NC

 

Normally Closed

 

 

 

 

 

4.4.4. State

 

 

 

 

 

 

 

 

 

Handheld programmer

OFF

*

Relay de-energized

 

options

ON

 

Relay energized

 

 

 

 

 

Certificates and Approvals