4.2. AIFB2
(See AIFB1: the parameters for AIFB2 are identical.)
4.3. mA Output
The mA output is provided by Analog Input Function Block 2 (AIFB2).You can enter a
To set these parameters via PDM, see Simulate AO (Analog Output) on page 42 or D/A (Digital/Analog) Trim on page 42.
4.3.1. Function
Allows you to set the mA output to one of three options including a
Handheld | AUTO | Uses the current measured value. | |
|
| ||
| The current can be set by the HART master only. | ||
programmer | FIXED | ||
HART default is 4 mA. | |||
values |
| ||
|
| ||
MANUAL | Uses a | ||
| |||
|
|
|
To set the mA output via PDM, open the menu Device – Simulate AO.
4.3.2. Out value
A mA value derived from the ratio of current level to the range between Lower Value and Upper Value.
Analog
Input
Function
Block 1
measured value
x
Upper Value = 20 mA
(4.1.7. Output Scale)
y
Lower Value = 4 mA
(4.1.7. Output Scale)
mA OUT value = x x 16 mA + 4 y
4.3.3. Man Value
A
Values | Range: 3.8 to 20.5 mA. |
To set the mA Output via PDM, open the menu Device – Simulate AO and select an option.
Parameters
7ML19985JM01 | SITRANS LR 460 – INSTRUCTION MANUAL | Page 65 |