Panel Calibration

2.Press the crosshairs (on the Calibration page) to set the calibration points on the LCD (FIG. 48).

The request to touch the crosshairs is the first on-screen message

Calibration successful is the second on-screen message that appears after the calibration process is completed

On-screen crosshairs used for calibration of the touch device

FIG. 48 Touch Panel Calibration Screens

3.After the "Calibration Successful.." message appears, press anywhere on the screen to continue and return to the Setup page.

If the calibration was improperly set and you cannot return to the Calibration page (through the panel’s firmware); you can access this firmware page via

G4 WebControl where you can navigate to the Protected Setup page and press the Calibrate button through your VNC window.

This action causes the panel to go to the Calibration page seen above, where you can physically recalibrate the actual touch panel again using the above procedures.

Testing your Calibration

1.Press and hold down the on-screen Calibration button for 6 seconds to enter the Calibration Test page (FIG. 49).

On-screen crosshairs is used to verify a proper calibration of the panel

FIG. 49 Calibration Test page

2.Press anywhere on this page to confirm the on-screen crosshairs match your touch points.

3.If the crosshairs do not appear directly below your LCD touch points, press the Back button and recalibrate the panel using the above steps.

4.Exit this Calibration Test page by pressing the Back button to return to the Protected Setup page.