Table 115 — Main Control Board (MBB) Inputs and Outputs

POINT

POINT DESCRIPTION

I/O POINT

PLUG AND PIN

SIGNAL PIN(S)

PORT STATE

NAME

NAME

REFERENCE

 

 

 

INPUTS

 

 

 

 

 

GASFAN

YAC Indoor Fan relay (fan request from YAC)

DI1

J6, 3-4

4

0 = 24vac, 1= 0vac

FSD

Fire Shutdown switch input

DI2

J6, 5-6

6

0 = 24vac, 1= 0vac

G

Thermostat ‘G’ input

DI3

J7, 1-2

2

0 = 24vac, 1= 0vac

W2

Thermostat ‘W2’ input

DI4

J7, 3-4

4

0 = 24vac, 1= 0vac

W1

Thermostat ‘W1’ input

DI5

J7, 5-6

6

0 = 24vac, 1= 0vac

Y2

Thermostat ‘Y2’ input

DI6

J7, 7-8

8

0 = 24vac, 1= 0vac

Y1

Thermostat ‘Y1’ input

DI7

J7, 9-10

10

0 = 24vac, 1= 0vac

CSB_A1

Compressor A1 current sensor

DIG1

J9, 10-12

10=5v, 11=Vin, 12=GND

0 = 5vdc, 1 = 0vdc

CSB_A2

Compressor A2 current sensor

DIG2

J9, 7-9

7=5v, 8=Vin, 9=GND

0 = 5vdc, 1 = 0vdc

CSB_B1

Compressor B1 current sensor

DIG3

J9, 4-6

4=5v, 5=Vin, 6 =GND

0 = 5vdc, 1 = 0vdc

CSB_B2

Compressor B2 current sensor

DIG4

J9, 1-3

1=5v, 2=Vin, 3=GND

0 = 5vdc, 1 = 0vdc

DP_A/SCTA

Circuit A saturated

AN1

J8, 21-23

21=5v, 22=Vin, 23=GND

(0-5vdc, thermistor, ohms)

condensing pressure/temp

(thermistor 21-22)

 

 

 

 

DP_B/SCTB

Circuit B saturated

AN2

J8, 24-26

24=5v, 25=Vin, 26=GND

(0-5vdc, thermistor, ohms)

condensing pressure/temp

(thermistor 24-25)

 

 

 

 

SP_A/SSTA

Circuit A saturated

AN3

J8, 15-17

15=5v, 16=Vin, 17=GND

(0-5vdc, thermistor, ohms)

suction pressure/temp

(thermistor 15-16)

 

 

 

 

SP_B/SSTB

Circuit B saturated

AN4

J8, 18-20

18=5v, 19=Vin, 20=GND

(0-5vdc, thermistor, ohms)

suction pressure/temp

(thermistor 18-20)

 

 

 

 

RAT

Return air temperature

AN5

J8, 9-10

9

(thermistor, ohms)

SA_TEMP

Supply air temperature

AN6

J8, 11-12

11

(thermistor, ohms)

OAT

Outdoor air temperature

AN7

J8, 13-14

13

(thermistor, ohms)

SPT

Space temperature (T55/56)

AN8

J8, 1-2

1

(thermistor, ohms)

SPTO

Space temperature offset (T56)

AN9

J8, 3-4

3

(thermistor, ohms)

IAQ/IAQMINOV

IAQ analog input

AN10

J8, 5-6

5

(thermistor, ohms)

FLTS

Filter Status

AN11

J8, 7-8

7

(thermistor, ohms)

OUTPUTS

 

 

 

 

 

CMPB2

Compressor B2

RLY 1

J10, 20-21

20 = RLY1A (=RLY2A), 21 = RLY1B

1 = Closes RLY1A/RLY1B

CMPB1

Compressor B1

RLY 2

J10, 22-23

22 = RLY2A (=RLY1A), 23 = RLY2B

1 = Closes RLY2A/RLY2B

CMPA2

Compressor A2

RLY 3

J10, 24-25

24 = RLY3A (=RLY4A), 25 = RLY3B

1 = Closes RLY3A/RLY3B

CMPA1

Compressor A1

RLY 4

J10, 26-27

26 = RLY4A (=RLY3A), 27 = RLY4B

1 = Closes RLY4A/RLY4B

CONDFANB

Condenser fan B

RLY 5

J10, 10-11

10 = RLY5A (=RLY6A), 11 = RLY5B

1 = Closes RLY5A/RLY5B

CONDFANA

Condenser fan A

RLY 6

J10, 12-13

12 = RLY6A (=RLY5A), 13 = RLY6B

1 = Closes RLY6A/RLY6B

HS2

Heat stage 2

RLY7

J10, 14-16

14 = 15 = RLY7A, 16 = RLY7B

1 = Closes RLY7A/RLY7B

HS1

Heat stage 1

RLY 8

J10, 17-19

17 = 18 = RLY8A, 19 = RLY8B

1 = Closes RLY8A/RLY8B

HIR

Heat interlock relay

RLY 9

J10, 4-6

4 = 5 = RLY9A, 6 = RLY9B

1 = Closes RLY9A/RLY9B

SF

Supply fan

RLY 10

J10, 7-9

7 = 8 = RLY10A, 9 = RLY10B

1 = Closes RLY10A/RLY10B

ALRM

Alarm output relay

RLY 11

J10, 1-3

1 = 2 = RLY11A, 3 = RLY11B

1 = Closes RLY11A/RLY11B

YAC — Gas Heat Unit

RED LED - STATUS

GREEN LED-

YELLOW LED -

 

LEN (LOCAL EQUIPMENT NETWORK)

CCN (CARRIER COMFORT NETWORK)

 

 

 

 

INSTANCE JUMPER (SET TO 1)

 

 

CEPL130346-01 HK 50AA029 CE BO 430346

 

J1

J2

 

STATUS

 

J4

J3

LEN

 

J10

 

 

 

 

 

 

 

 

J5

 

 

 

J6

 

 

 

 

 

 

 

A48-7811

 

 

 

J7

J8

J9

Fig. 26 — Main Base Board (MBB)