Table 67 — Mode Trip Helper Table

ITEM

EXPANSION

 

UNITS

 

CCN POINT

TRIP

MODE TRIP HELPER

 

 

 

 

UN.C.S

Unoccup. Cool Mode Start

 

dF

 

UCCLSTRT

 

 

UN.C.E

Unoccup. Cool Mode End

 

dF

 

UCCL_END

OC.C.S

Occupied Cool Mode Start

 

dF

 

OCCLSTRT

OC.C.E

Occupied Cool Mode End

 

dF

 

OCCL_END

TEMP

Ctl.Temp RAT,SPT or Zone

 

dF

 

CTRLTEMP

OC.H.E

Occupied Heat Mode End

 

dF

 

OCHT_END

OC.H.S

Occupied Heat Mode Start

 

dF

 

OCHTSTRT

UN.H.E

Unoccup. Heat Mode End

 

dF

 

UCHT_END

UN.H.S

Unoccup. Heat Mode Start

 

dF

 

UCHTSTRT

HVAC

the current HVAC MODE

 

 

 

String

If the HVAC mode is HIGH HEAT:

If Electric Heat is configured, then the control will request the supply fan ON

If Gas Heat is configured, then the IGC indoor fan input controls the supply fan request

The control will turn on Heat Relay 1 (HS1)

The control will turn on Heat Relay 2 (HS2)

*The logic for this “low heat” override is that one stage of heating will not be able to raise the temperature of the supply airstream sufficient to heat the space.

HT.CF = 3 (Staged Gas Heating Control) — As an option, the units with gas heat can be equipped with staged gas heat controls that will provide from 5 to 11 stages of heat capacity. This is intended for tempering mode and tempering economizer air when in a cooling mode and the dampers are fully closed. Tempering can also be used during a pre- occupancy purge to prevent low temperature air from being delivered to the space. Tempering for staged gas will be dis- cussed in its own section. This section will focus on heat mode control, which ultimately is relevant to tempering, minus the consideration of the supply air heating control point.

The staged gas configurations are located at the local display under ConfigurationHEATSG.CF. See Table 68.

Staged Gas Heat Type (HT.ST) — This configuration sets the number of stages and the order that are they staged.

Max Cap Change per Cycle (CAP.M) — This configuration limits the maximum change in capacity per PID run time cycle.

S.Gas DB Min.dF/PID Rate (M.R.DB) — This configuration is a deadband minimum temperature per second rate. See Staged Gas Heating logic below for more details.

St.Gas Temp.Dead Band (S.G.DB) — This configuration is a deadband delta temperature. See Staged Gas Heating logic below for more details.

Heat Rise in dF/Sec Clamp (RISE) — This configuration prevents the heat from staging up when the leaving-air temper- ature is rising too fast.

LAT Limit Config (LAT.L) — This configuration senses when leaving-air temperature is outside a delta temperature band around set point and allows staging to react quicker.

Limit Switch Monitoring? (LIM.M) — This configuration allows the operation of the limit switch monitoring routine. This should be set to NO as a limit switch temperature sensor is not used with A Series units.

Limit Switch High Temp (SW.H.T) — This configuration is the temperature limit above which stages of heat will be removed.

Limit Switch Low Temp (SW.L.T) — This configuration is the temperature limit above which no additional stages of heat will be allowed.

Heat Control Prop. Gain (HT.P) — This configuration is the proportional term for the PID which runs in the HVAC mode

LOW HEAT.

Heat Control Derv. Gain (HT.D) — This configuration is the derivative term for the PID which runs in the HVAC mode

LOW HEAT.

Heat PID Rate Config (HT.TM) — This configuration is the PID run time rate.

Staged Gas Heating Logic

If the HVAC mode is HIGH HEAT:

The supply fan for staged gas heating is controlled by the integrated gas control (IGC) boards and, unless the supply fan is on for a different reason, it will be con- trolled by the IGC indoor fan input.

Command all stages of heat ON

If the HVAC mode is LOW HEAT:

The supply fan for staged gas heating is controlled by the integrated gas control (IGC) boards and, unless the supply fan is on for a different reason, it will be con- trolled by the IGC indoor fan input.

The unit will control stages of heat to the heating control point (Run StatusVIEWHT.C.P). The heating con- trol point in a LOW HEAT HVAC mode for staged gas is the heating supply air set point (SetpointsSA.HT).

Staged Gas Heating PID Logic — The heat control loop is a PID (proportional/integral/derivative) design with exceptions, overrides, and clamps. Capacity rises and falls based on set point and supply-air temperature. When the staged gas control is in Low Heat or Tempering Mode (HVAC mode), the algo- rithm calculates the desired heat capacity. The basic factors that govern the controlling method are:

how fast the algorithm is run.

the amount of proportional and derivative gain applied.

the maximum allowed capacity change each time this algorithm is run.

deadband hold-off range when rate is low.

This routine is run once every HT.TM seconds. Every time the routine is run, the calculated sum is added to the control output value. In this manner, integral effect is achieved. Every time this algorithm is run, the following calculation is performed:

Error = HT.C.P LAT

Error_last = error calculated previous time P = HT.P*(Error)

D = HT.D*(Error - Error_last)

The P and D terms are overridden to zero if:

Error < S.G.DB AND Error > - S.G.DB AND D < M.R.DB AND D > - M.R.DB. “P + D” are then clamped based on CAP.M. This sum can be no larger or no smaller than +CAP.M or CAP.M.

Finally, the desired capacity is calculated:

Staged Gas Capacity Calculation = “P + D” + old Staged Gas Capacity Calculation

NOTE: The PID values should not be modified without approval from Carrier.

IMPORTANT: When gas or electric heat is used in a VAV application with third party terminals, the HIR relay output must be connected to the VAV terminals in the system in order to enforce a minimum heating airflow rate. The installer is responsible to ensure the total minimum heating cfm is not below limits set for the equipment. Failure to do so will result in limit switch tripping and may void warranty.

53

Page 53
Image 53
Carrier 48/50AJ specifications Mode Trip Helper Table, Expansion Units CCN Point