Carrier 48/50AJ specifications Time Clock Configuration

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 75
Image 75

Table 89 — Switch Logic Configuration

ITEM

EXPANSION

 

RANGE

 

CCN POINT

 

DEFAULT

SW.LG

SWITCH LOGIC: NO / NC

 

 

 

 

 

 

FTS.L

Filter Status Inpt-Clean

 

Open/Close

 

FLTSLOGC

 

Open

 

 

 

IGC.L

IGC Feedback - Off

 

Open/Close

 

GASFANLG

 

Open

RMI.L

RemSw Off-Unoc-Strt-NoOv

 

Open/Close

 

RMTINLOG

 

Open

ECS.L

Economizer Switch - No

 

Open/Close

 

ECOSWLOG

 

Open

SFS.L

Fan Status Sw. - Off

 

Open/Close

 

SFSLOGIC

 

Open

DL1.L

Dmd.Lmt.Sw.1 - Off

 

Open/Close

 

DMD_SW1L

 

Open

DL2.L

Dmd.Lmt.2 Dehumid - Off

 

Open/Close

 

DMD_SW2L

 

Open

IAQ.L

IAQ Disc.Input - Low

 

Open/Close

 

IAQINLOG

 

Open

FSD.L

Fire Shutdown - Off

 

Open/Close

 

FSDLOGIC

 

Open

PRS.L

Pressurization Sw. - Off

 

Open/Close

 

PRESLOGC

 

Open

EVC.L

Evacuation Sw. - Off

 

Open/Close

 

EVACLOGC

 

Open

PRG.L

Smoke Purge Sw. - Off

 

Open/Close

 

PURGLOGC

 

Open

Table 90 — Display Configuration

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

TEST

Test Display LEDs

ON/OFF

 

TEST

Off

METR

Metric Display

ON/OFF

 

DISPUNIT

Off

LANG

Language Selection

0-1(multi-text strings)

 

LANGUAGE

0

PAS.E

Password Enable

ENABLE/DISABLE

 

PASS_EBL

Enable

PASS

Service Password

0000-9999

 

PASSWORD

1111

Table 91 — Remote Switch Configuration

ITEM

EXPANSION

RANGE

CCN

POINT

 

 

 

REMT

Remote Input State

ON/OFF

RMTIN

RM.CF

Remote Switch Config

0 - 3

RMTINCFG

RMI.L

RemSw

Open/Close

RMTINLOG

 

Off-Unoc-Strt-NoOv

 

 

Remote Switch Logic Configuration (ConfigurationSW.LGRMI.L) — The control allows for the configuration of a normally open/closed status of the remote input switch via RMI.L. If this variable is configured OPEN, then when the switch is open, the remote input switch perceives the logic state as OFF. Correspondingly, if RMI.L is set to CLOSED, the re- mote input switch will perceive a closed switch as meaning OFF. See Table 92.

Hot Gas Bypass — Hot gas bypass is an active part of the A-Series ComfortLink™ capacity staging and minimum evaporator load protection functions. It is controlled though the Minimum Load Valve function.

The hot gas bypass option consists of a solenoid valve with a fixed orifice sized to provide a nominal 3-ton evaporator load bypass. A hot gas refrigerant line routes the bypassed hot gas from Circuit A’s discharge line to Circuit A’s evaporator distributor. When the unit control calls for hot gas bypass, the hot gas enters the evaporator coil and adds refrigeration load to the compressor circuit to reduce the cooling effect from Circuit A.

The hot gas bypass system is a factory-installed option installed on Circuit A only. This function is enabled at Config- urationCOOLMLV. When this function is enabled, an additional stage of cooling capacity is provided by the unit control staging sequences (see Tables 52, 54, 58, and 60).

Space Temperature Offset — Space temperature off- set corresponds to a slider on a T56 sensor that allows the occu- pant to adjust the space temperature by a configured range during an occupied period. This sensor is only applicable to units that are configured as either 2-Stage SPT or Multi-Stage SPT control (ConfigurationUNITC.TYP = 5 or 6).

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

 

 

 

 

SP.O.S

Space Temp

Enable/

 

SPTOSENS

 

Offset Sensor

Disable

 

 

SP.O.R

Space Temp

1 - 10

 

SPTO_RNG

 

Offset Range

 

 

 

SPTO

Space Temperature

+- SP.O.R

^F

SPTO

 

Offset

 

 

 

Space Temperature Offset Sensor (ConfigurationUNIT SENSSP.O.S) — This configuration disables the reading of the offset slider.

Space Temperature Offset Range (Configuration UNITSENSSP.O.R) — This configuration establishes the range, in degrees F, that the T56 slider can affect SPTO when adjusting the slider from the far left (-SP.O.R) to the far right (+SP.O.R). The default is 5° F.

Space Temperature Offset Value (TemperaturesAIR.T SPTO) — The Space Temperature Offset Value is the read- ing of the slider potentiometer in the T56 that is resolved to delta degrees based on SP.O.R.

TIME CLOCK CONFIGURATION

This section describes each Time Clock menu item. Not every point will need to be configured for every unit. Refer to the Controls Quick Start section for more information on what set points need to be configured for different applications. The Time Clock menu items are discussed in the same order that they are displayed in the Time Clock table. The Time Clock table is shown in Table 93.

Hour and Minute (HH.MM) — The hour and minute of the time clock are displayed in 24-hour, military time. Time can be adjusted manually by the user.

When connected to the CCN, the unit can be configured to transmit time over the network or receive time from a network device. All devices on the CCN should use the same time. Only one device on the CCN should broadcast time or problems will occur.

Month of Year (MNTH) — This variable is the current month of the calendar year.

Day of Month (DOM) — This variable is the current day (1 to 31) of the month.

Day of Week (DAY) — This variable is the current day of the week (Monday = 1 through Sunday = 7).

Year (YEAR) — This variable is the current year (for ex- ample, 2005).

Local Time Schedule (SCH.L) — This submenu is used to program the time schedules. There are 8 periods (PER.1 through PER.8). Each time period can be used to set up a local schedule for the unit.

75