Carrier 48/50AJ specifications NETWORK POINTS LIST cont, APPENDIX E — UPC OPEN CONTROLLER cont

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 177
Image 177

APPENDIX E — UPC OPEN CONTROLLER (cont)

NETWORK POINTS LIST (cont)

BACNET

POINT NAME

READ

UNITS

DEFAULT

RANGE

BACNET

UNIT

OBJECT ID

ONLY

VALUE

OBJECT NAME

POINT

 

 

 

 

 

 

 

 

 

 

 

AV:61

Dmd Level(+) Hi Cool ON

W

°^F

0.5

0.5-20

dmdhcon_1

DMDHCON

 

 

 

 

 

 

 

 

AV:62

Dmd Level(+) Hi Heat ON

W

°^F

0.5

0.5-20

dmdhhon_1

DMDHHON

 

 

 

 

 

 

 

 

AV:63

Dmd Level Low Cool ON

W

°^F

1.5

0.5-2

dmdlcon_1

DMDLCON

 

 

 

 

 

 

 

 

AV:64

Dmd Level Low Heat ON

W

°^F

1.5

0.5-2

dmdlhon_1

DMDLHON

 

 

 

 

 

 

 

 

AV:66

Econo Current Min. Pos.

R

%

n/a

n/a

min_pos_1

MIN_POS

 

 

 

 

 

 

 

 

AV:67

Economizer Act. Cmd. Pos.

W

%

n/a

0-100

econocmd_1

ECONOCMD

 

 

 

 

 

 

 

 

AV:68

Economizer Control Point

R

°F

n/a

n/a

econpnt_1

ECONCPNT

 

 

 

 

 

 

 

 

AV:70

Economizer Max.Position

W

%

98

0-100

economax_1

ECONOMAX

 

 

 

 

 

 

 

 

AV:76

Evaporator Discharge Tmp

R

°F

n/a

n/a

edt_1

EDT

 

 

 

 

 

 

 

 

AV:77

Fan Mode

W

n/a

1

0-1

fan_mode_1

FAN_MODE

 

 

 

 

 

 

 

 

AV:78

Fan-Off Delay, Elec Heat

W

n/a

30

10-600

elec_fod_1

ELEC_FOD

 

 

 

 

 

 

 

 

AV:79

Fan-Off Delay, Gas Heat

W

n/a

45

45-600

gas_fod_1

GAS_FOD

 

 

 

 

 

 

 

 

AV:80

Fan-Off Delay, Mech Cool

W

sec

60

0-600

cool_fod_1

COOL_FOD

 

 

 

 

 

 

 

 

AV:83

Heat-Cool Setpoint Gap

W

°^F

5

2-10

hcsp_gap_1

HCSP_GAP

 

 

 

 

 

 

 

 

AV:85

Heating Supply Air Setpt

W

°F

85

80-120

saspheat_1

SASPHEAT

 

 

 

 

 

 

 

 

AV:86

High BP Level

W

n/a

0.05

0-1

bphplvl_1

BPHPLVL

 

 

 

 

 

 

 

 

AV:87

Low BP Level

W

n/a

0.04

0-1

bplplvl_1

BPLPLVL

 

 

 

 

 

 

 

 

AV:93

IAQ Econo Override Pos.

W

%

100

0-100

iaqovpos_1

IAQOVPOS

 

 

 

 

 

 

 

 

AV:95

IAQ High Reference

W

n/a

2000

0-5000

iaqrefh_1

IAQREFH

 

 

 

 

 

 

 

 

AV:96

IAQ Low Reference

W

n/a

0

0-5000

iaqrefl_1

IAQREFL

 

 

 

 

 

 

 

 

AV:97

IAQ Min.Pos.Override

W

%

n/a

0-100

iaqminov_1

IAQMINOV

 

 

 

 

 

 

 

 

AV:98

IAQ Purge Duration

W

min

15

5-60

iaqptime_1

IAQPTIME

 

 

 

 

 

 

 

 

AV:99

IAQ Purge HiTemp Min Pos

W

%

35

0-100

iaqphtmp_1

IAQPHTMP

 

 

 

 

 

 

 

 

AV:100

IAQ Purge LoTemp Min Pos

W

%

10

0-100

iaqpltmp_1

IAQPLTMP

 

 

 

 

 

 

 

 

AV:101

IAQ Purge OAT Lockout

W

°F

50

35-70

iaqpntlo_1

IAQPNTLO

 

 

 

 

 

 

 

 

AV:102

LAT Limit Config

W

°^F

10

0-20

htlatlim_1

HTLATLIM

 

 

 

 

 

 

 

 

AV:107

Maximum Heat Stages

R

n/a

n/a

n/a

htmaxstg_1

HTMAXSTG

 

 

 

 

 

 

 

 

AV:112

OAQ Lockout Value

W

n/a

0

0-2000

oaqlock_1

OAQLOCK

 

 

 

 

 

 

 

 

AV:113

OAQ - PPM Outdoor CO2

W

n/a

n/a

0-5000

oaq_1

OAQ

 

 

 

 

 

 

 

 

AV:114

Occupied Cool Mode End

R

°F

n/a

n/a

occl_end_1

OCCL_END

 

 

 

 

 

 

 

 

AV:115

Occupied Cool Mode Start

R

°F

n/a

n/a

occlstrt_1

OCCLSTRT

 

 

 

 

 

 

 

 

AV:116

Occupied Heat Mode End

R

°F

n/a

n/a

ocht_end_1

OCHT_END

 

 

 

 

 

 

 

 

AV:117

Occupied Heat Mode Start

R

°F

n/a

n/a

ochtstrt_1

OCHTSTRT

 

 

 

 

 

 

 

 

AV:118

Outside Air Humidity Ratio

R

n/a

n/a

n/a

oa_humr_1

OA_HUMR

 

 

 

 

 

 

 

 

AV:119

Outside Air Relative Humidity

W

%

n/a

0-100

oarh_1

OARH

 

 

 

 

 

 

 

 

AV:120

Override Time Limit

W

hr

1

0-4

otl_1

OTL

 

 

 

 

 

 

 

 

AV:121

Power Exhaust Motors

W

n/a

1

0-2

pwrm_1

PWRM

 

 

 

 

 

 

 

 

AV:122

Power Exhaust On Setp.1

W

%

35

0-100

pes1_1

PES1

 

 

 

 

 

 

 

 

AV:123

Power Exhaust On Setp.2

W

%

75

0-100

pes2_1

PES2

 

 

 

 

 

 

 

 

AV:130

Remote Switch Config

W

n/a

0

0-3

rmtincfg_1

RMTINCFG

 

 

 

 

 

 

 

 

AV:131

Reset Limit

W

°^F

10

0-20

limt_1

LIMT

 

 

 

 

 

 

 

 

AV:132

Reset Ratio

W

n/a

2

0-10

rtio_1

RTIO

 

 

 

 

 

 

 

 

AV:133

Return Air Enthalpy

R

n/a

n/a

n/a

rae_1

RAE

 

 

 

 

 

 

 

 

See legend on page 182.