APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM | EXPANSION |
| RANGE | UNITS | CCN POINT | DEFAULT | PAGE NO. |
COOL | COOLING CONFIGURATION |
|
|
|
|
|
|
→Z.GN | Capacity Threshold Adjst |
| Z_GAIN | 1 | 39,46,91 | ||
→MC.LO | Compressor Lockout Temp | dF | OATLCOMP | 40 | 39,48 | ||
→C.FOD | 0 | - 600 | sec | COOL_FOD | 60 | 39 | |
→MLV | Min. Load Valve? (HGBP) | Yes/No |
| MLV_SEL | No | 39,75 | |
→M.M. | Motor Master Control | Yes/No |
| MOTRMAST | No | 39,49 | |
→HPSP | Head Pressure Setpoint | 80 - 150 | dF | HPSP | 113 | 39,49 | |
→A1.EN | Enable Compressor A1 | Enable/Disable |
| CMPA1ENA | Enable | 39 | |
→A2.EN | Enable Compressor A2 | Enable/Disable |
| CMPA2ENA | Enable | 39 | |
→B1.EN | Enable Compressor B1 | Enable/Disable |
| CMPB1ENA | Enable | 39 | |
→B2.EN | Enable Compressor B2 | Enable/Disable |
| CMPB2ENA | Enable | 39 | |
→CS.A1 | CSB A1 Feedback Alarm | Enable/Disable |
| CSB_A1EN | Enable | 39,100 | |
→CS.A2 | CSB A2 Feedback Alarm | Enable/Disable |
| CSB_A2EN | Enable | 39,100 | |
→CS.B1 | CSB B1 Feedback Alarm | Enable/Disable |
| CSB_B1EN | Enable | 39,100 | |
→CS.B2 | CSB B2 Feedback Alarm | Enable/Disable |
| CSB_B2EN | Enable | 39,100 | |
→REV.R | Rev Rotation Verified ? | Yes/No |
| REVR_VER | No | 39,98 | |
→H.SST | Hi SST Alert Delay Time | 5 | - 30 | min | HSSTTIME | 10 | 39,97 |
EDT.R | EVAP.DISCHRGE TEMP RESET |
|
|
|
|
|
|
→RS.CF | EDT Reset Configuration | 0 | - 3 |
| EDRSTCFG | 0 | 28,38 |
→RTIO | Reset Ratio | 0 | - 10 |
| RTIO | 2 | 28,38 |
→LIMT | Reset Limit | 0 | - 20 | ^F | LIMT | 10 | 28,38 |
→RES.S | EDT | Enable/Disable |
| EDTRSENS | Disable | 28,35,38,96 | |
HEAT | HEATING CONFIGURATION |
|
|
|
|
|
|
→HT.CF | Heating Control Type | 0 | - 4 |
| HEATTYPE | 0 | 50,51,56,71 |
→HT.SP | Heating Supply Air Setpt | 80 - 120 | dF | SASPHEAT | 85 | 50,51 | |
→OC.EN | Occupied Heating Enabled | Yes/No |
| HTOCCENA | No | 51 | |
→LAT.M | MBB Sensor Heat Relocate | Yes/No |
| HTLATMON | No | 51 | |
→G.FOD |
| GAS_FOD | 45 | 51 | |||
→E.FOD |
| HEAT_FOD | 30 | 51 | |||
→SG.CF | STAGED GAS CONFIGS |
|
|
|
|
|
|
→SG.CF→HT.ST | Staged Gas Heat Type | 0 | - 4 |
| HTSTGTYP | 0 | |
→SG.CF→CAP.M | Max Cap Change per Cycle | 5 | - 45 |
| HTCAPMAX | 45 | 51,53,54 |
→SG.CF→M.R.DB | S.Gas DB min.dF/PID Rate | 0 | - 5 |
| HT_MR_DB | 0.5 | 51,53,54 |
→SG.CF→S.G.DB | St.Gas Temp. Dead Band | 0 | - 5 | ^F | HT_SG_DB | 2 | 51,53,54 |
→SG.CF→RISE | Heat Rise dF/sec Clamp | 0.05 - 0.2 |
| HTSGRISE | 0.06 | 51,53,54 | |
→SG.CF→LAT.L | LAT Limit Config | 0 | - 20 | ^F | HTLATLIM | 10 | 51,53,54 |
→SG.CF→LIM.M | Limit Switch Monitoring? | Yes/No |
| HTLIMMON | No | 51,53,54 | |
→SG.CF→SW.H.T | Limit Switch High Temp | 110 - 180 | dF | HT_LIMHI | 170 | 51,53,54 | |
→SG.CF→SW.L.T | Limit Switch Low Temp | 100 - 170 | dF | HT_LIMLO | 160 | 51,53,54 | |
→SG.CF→HT.P | Heat Control Prop. Gain | 0 | - 1.5 |
| HT_PGAIN | 1 | 51,53,54 |
→SG.CF→HT.D | Heat Control Derv. Gain | 0 | - 1.5 |
| HT_DGAIN | 1 | 51,53,54 |
→SG.CF→HT.TM | Heat PID Rate Config | 60 - 300 | sec | HTSGPIDR | 90 | 51,53,54 | |
SP | SUPPLY STATIC PRESS.CFG. |
|
|
|
|
|
|
→SP.CF | Static Pressure Config | 0 | - 1 |
| STATICFG | No | 31,57,58,60 |
→SP.FN | Static Pres.Fan Control? | Yes |
| STATPFAN | Yes | 57,58 | |
→SP.S | Static Pressure Sensor | Enable/Disable |
| SPSENS | Disable | 57,58 | |
→SP.LO | Static Press. Low Range |
| SP_LOW | 0 | 57,58 | ||
→SP.HI | Static Press. High Range | 0 | - 10 |
| SP_HIGH | 5 | 57,58 |
→SP.SP | Static Pressure Setpoint | 0 | - 5 | "H2O | SPSP | 1.5 | 28,57,58 |
→SP.MN | VFD Minimum Speed | 0 | - 100 | % | STATPMIN | 20 | 58 |
→SP.MX | VFD Maximum Speed | 0 | - 100 | % | STATPMAX | 100 | 58 |
→SP.FS | VFD Fire Speed Override | 0 | - 100 | % | STATPFSO | 100 | 58,67 |
→SP.RS | Stat. Pres. Reset Config |
| SPRSTCFG | 0 | 31,58,59 | ||
→SP.RT | SP Reset Ratio (″/dF) | 0 | - 2.00 |
| SPRRATIO | 0.2 | 58 |
→SP.LM | SP Reset Limit in iwc(″) | 0 | - 2.00 |
| SPRLIMIT | 0.75 | 58 |
→SP.EC | SP Reset Econo.Position | 0 | - 100 | % | ECONOSPR | 5 | 58 |
→S.PID | STAT.PRESS.PID CONFIGS |
|
|
|
|
| 58,59 |
Stat.Pres.PID Run Rate | 1 | - 200 | sec | SPIDRATE | 2 | 58,59 | |
Static Press. Prop. Gain | 0 | - 100 |
| STATP_PG | 20 | 58,59 | |
Static Pressure Intg. Gain | 0 | - 50 |
| STATP_IG | 2 | 58,59 | |
Static Pressure Derv. Gain | 0 | - 50 |
| STATP_DG | 0 | 58,59 | |
Static Press.System Gain | 0 | - 50 |
| STATP_SG | 1 | 58,59 | |
ECON | ECONOMIZER CONFIGURATION |
|
|
|
|
|
|
→EC.EN | Economizer Installed? | Yes/No |
| ECON_ENA | Yes | 28,60,62 | |
→EC.MN | Economizer Min.Position | 0 | - 100 | % | ECONOMIN | 5 | 28,60,62 |
→EC.MX | Economizer Max.Position | 0 | - 100 | % | ECONOMAX | 98 | 28,42,43,50,60, |
→E.TRM |
|
|
|
|
|
| 62 |
Economzr Trim For SumZ ? | Yes/No |
| ECONTRIM | Yes | 28,48,60,62 | ||
→E.SEL | Econ ChangeOver Select | 0 | - 3 |
| ECON_SEL | 1 | 28,61,62 |
→OA.E.C | OA Enthalpy ChgOvr Selct | 1 | - 5 |
| OAEC_SEL | 4 | 28,61,62 |
→OA.EN | Outdr.Enth Compare Value | 18 - 28 |
| OAEN_CFG | 24 | 28,61,62 | |
→OAT.L | High OAT Lockout Temp | dF | OAT_LOCK | 60 | 28,61,62 | ||
→O.DEW | OA Dewpoint Temp Limit | 50 - 62 | dF | OADEWCFG | 55 | 28,61,62 | |
→ORH.S | Outside Air RH Sensor | Enable/Disable |
| OARHSENS | Disable | 28,61,62,96 | |
→E.TYP | Economizer Control Type |
| ECON_CTL | 1 | 61,62 | ||
→EC.SW | Economizer Switch Config | 0 | - 2 |
| ECOSWCFG | 0 | 61,62 |
→E.CFG | ECON.OPERATION CONFIGS |
|
|
|
|
|
|
→E.CFG→E.P.GN | Economizer Prop.Gain | 0.7 - 3.0 |
| EC_PGAIN | 1 | 62 | |
→E.CFG→E.RNG | Economizer Range Adjust | 0.5 - 5.0 | ^F | EC_RANGE | 2.5 | 62 | |
→E.CFG→E.SPD | Economizer Speed Adjust | 0.1 - 10.0 |
| EC_SPEED | 0.75 | 62 | |
→E.CFG→E.DBD | Economizer Deadband | 0.1 - 2.0 | ^F | EC_DBAND | 0.5 | 62 | |
→UEFC | UNOCC.ECON.FREE COOLING |
|
|
|
|
|
|
→UEFC→FC.CF | Unoc Econ Free Cool Cfg |
| UEFC_CFG | 0 | 62 | ||
→UEFC→FC.TM | Unoc Econ Free Cool Time | 0 | - 720 | min | UEFCTIME | 120 | 62 |
→UEFC→FC.L.O | Un.Ec.Free Cool OAT Lock | 40 - 70 | dF | UEFCNTLO | 50 | 62 |