Carrier 48/50AJ specifications Economizer Run Status Table

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 64
Image 64

Table 80 — Economizer Run Status Table

ITEM

EXPANSION

 

RANGE

 

UNITS

 

CCN POINT

 

WRITE STATUS

ECN.P

Economizer Act.Curr.Pos.

 

0-100

 

%

 

ECONOPOS

 

 

ECN.C

Economizer Act.Cmd.Pos.

 

0-100

 

%

 

ECONOCMD

 

forcible

ACTV

Economizer Active ?

 

YES/NO

 

 

 

ECACTIVE

 

 

DISA

ECON DISABLING CONDITIONS

 

 

 

 

 

 

 

 

UNAV

Econ Act. Unavailable?

 

YES/NO

 

 

 

ECONUNAV

 

 

 

 

 

 

 

 

R.EC.D

Remote Econ. Disabled?

 

YES/NO

 

 

 

ECONDISA

 

 

DBC

DBC - OAT Lockout?

 

YES/NO

 

 

 

DBC_STAT

 

 

DEW

DEW - OA Dewpt.Lockout?

 

YES/NO

 

 

 

DEW_STAT

 

 

DDBC

DDBD- OAT > RAT Lockout?

 

YES/NO

 

 

 

DDBCSTAT

 

 

OAEC

OAEC- OA Enth Lockout?

 

YES/NO

 

 

 

OAECSTAT

 

 

DEC

DEC - Diff.Enth.Lockout?

 

YES/NO

 

 

 

DEC_STAT

 

 

EDT

EDT Sensor Bad?

 

YES/NO

 

 

 

EDT_STAT

 

 

OAT

OAT Sensor Bad ?

 

YES/NO

 

 

 

OAT_STAT

 

 

FORC

Economizer Forced ?

 

YES/NO

 

 

 

ECONFORC

 

 

SFON

Supply Fan Not On 30s ?

 

YES/NO

 

 

 

SFONSTAT

 

 

CLOF

Cool Mode Not In Effect?

 

YES/NO

 

 

 

COOL_OFF

 

 

OAQL

OAQ Lockout in Effect ?

 

YES/NO

 

 

 

OAQLOCKD

 

 

HELD

Econ Recovery Hold Off?

 

YES/NO

 

 

 

ECONHELD

 

 

DH.DS

Dehumid. Disabled Econ.?

 

YES/NO

 

 

 

DHDISABL

 

 

O.AIR

OUTSIDE AIR INFORMATION

 

 

 

 

 

 

 

 

OAT

Outside Air Temperature

 

 

 

dF

 

OAT

 

forcible

 

 

 

 

 

OA.RH

Outside Air Rel. Humidity

 

 

 

%

 

OARH

 

forcible

OA.E

Outside Air Enthalpy

 

 

 

 

 

OAE

 

 

OA.D.T

Outside Air Dewpoint Temp

 

 

 

dF

 

OADEWTMP

 

 

Building Pressure Config (BP.CF) — This configuration se- lects the type of building pressure control.

BP.CF = 0, No building pressure control

BP.CF = 1, constant volume two-stage power exhaust based on economizer position

BP.CF = 2, multiple stage building pressure control based on a building pressure sensor

BP.CF = 3, VFD building pressure control based on a building pressure sensor

Building Pressure PID Run Rate (BP.RT) — This configura- tion selects the run time of the PID algorithm. This configura- tion is only active when BP.CF = 3. It is recommended that this value not be changed without guidance from Service Engineering.

Building Pressure Proportional Gain (BP.P) — This configura- tion selects the proportional gain of the PID algorithm. This configuration is only active when BP.CF = 3. It is recommend- ed that this value not be changed without guidance from Service Engineering.

Building Pressure Integral Gain (BP.I) — This configuration selects the integral gain of the PID algorithm. This configuration is only active when BP.CF = 3. It is recommended that this val- ue not be changed without guidance from Service Engineering.

Building Pressure Derivative Gain (BP.D) — This configura- tion selects the derivative gain of the PID algorithm. This con- figuration is only active when BP.CF = 3. It is recommended that this value not be changed without guidance from Service Engineering.

Building Pressure Set Point Offset (BP.SO) — This configura- tion is the value below the building pressure set point to which the building pressure must fall in order to turn off power exhaust control. This configuration is only active when BP.CF = 3.

Building Pressure Minimum Speed (BP.MN) — This configu- ration is the minimum allowed VFD speed during building pres- sure control. This configuration is only active when BP.CF = 3.

Building Pressure Maximum Speed (BP.MX) — This configu- ration is the maximum allowed VFD speed during building pressure control. This configuration is only active when BP.CF = 3.

VFD Fire Speed (BP.FS) — This configuration is the VFD speed override when the control is in the purge or evacuation smoke control modes. This configuration is only active when BP.CF = 3.

Power Exhaust Motors (BP.MT) — This configuration is ma- chine dependent and instructs the building pressure control

algorithm as to whether the unit has 4 or 6 motors to control. The motors are controlled by three power exhaust relays A, B, and C. These relay outputs are located at the local display un- der OutputsFANSPE.A,B,C.

The following table illustrates the number of motors each relay is in control of based on BP.MT:

BP.MT

PE_A Relay

PE_B Relay

PE_C Relay

1 (4 motors)

1 Motor

2 Motors

1 Motor

2 (6 motors)

1 Motor

2 Motors

3 Motors

Building Pressure Sensor (BP.S) — This configuration al- lows the reading of a building pressure sensor when enabled. This is automatically enabled when BP.CF = 2 or 3.

Building Pressure (+/–) Range (BP.R) — This configuration establishes the range in in. wg that a 4 to 20 mA sensor will be scaled to. The control only allows sensors that measure both positive and negative pressure.

Building Pressure SETP (BP.SP) — This set point is the building pressure control set point. If the unit is configured for modulating building pressure control, then this is the set point that the control will control to.

Power Exhaust on Setp.1 (BP.P1) — When configured for building pressure control type BP.CF = 1 (constant volume two- stage control), the control will turn on the first power exhaust fan when the economizer’s position exceeds this set point.

Power Exhaust on Setp.1 (BP.P2) — When configured for building pressure control type BP.CF = 1 (constant volume two- stage control), the control will turn on the second power exhaust fan when the economizer’s position exceeds this set point.

Modulating PE Algorithm Select (BP.SL) — This configuration selects the algorithm used to step the power exhaust stages. This must be set to 1 at all times. The other selections are not used.

Building Pressure PID Evaluation Time (BP.TM) — This configuration is the run time rate of the multiple stage (modu- lating) power exhaust algorithm (BP.CF=2).

Building Pressure Threshold Adjustment (BP.ZG) — This configuration is not used. It currently has no effect on building pressure control.

High Building Pressure Level (BP.HP) — This configura- tion is the threshold level above the building pressure set point used to control stages of power exhaust when BP.SL=1.

Low Building Pressure Level (BP.LP) — This configuration is the threshold level below the building pressure set point used to control stages of power exhaust when BP.SL=1.

64

Page 64
Image 64
Carrier 48/50AJ specifications Economizer Run Status Table