APPENDIX B — CCN TABLES (cont)

SET POINT TABLE

TABLE

NAME

RANGE

UNITS

POINT NAME

DEFAULT

SET_PNT

Occupied Heat Setpoint

40-99

dF

OHSP

68

 

 

Occupied Cool Setpoint

40-99

dF

OCSP

75

 

Unoccupied Heat Setpoint

40-99

dF

UHSP

55

 

Unoccupied Cool Setpoint

40-99

dF

UCSP

90

 

Heat-Cool Setpoint Gap

2-10

^F

HCSP_GAP

5

 

VAV Occ. Cool On Delta

0-25

^F

VAVOCON

3.5

 

VAV Occ. Cool Off Delta

1-25

^F

VAVOCOFF

2

 

Supply Air Setpoint

45-75

dF

SASP

55

 

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

 

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

 

Heating Supply Air Setpt

80-100

dF

SASPHEAT

85

 

Tempering Purge SASP

–20-80

dF

TEMPPURG

50

 

Tempering in Cool SASP

5-75

dF

TEMPCOOL

5

 

Tempering in Vent Occ SASP

–20-80

dF

TEMPVOCC

65

 

Tempering Vent Unocc. SASP

–20-80

dF

TEMPVUNC

50

CONFIG TABLES

TABLE

NAME

RANGE

UNITS

POINT NAME

DEFAULT

ALARMDEF

Alarm Routing Control

00000000-11111111

 

ALRM_CNT

11000000

 

 

 

Equipment Priority

0 - 7

 

EQP_TYPE

5

 

Comm Failure Retry Time

1 - 240

min

RETRY_TM

10

 

Re-Alarm Time

1 - 255

min

RE-ALARM

30

 

Alarm System Name

up to 8 alphanum

 

ALRM_NAM

A-SERIES

BRODEFS

CCN Time/Date Broadcast

Off/On

 

CCNBC

Off

 

 

 

CCN OAT Broadcast

Off/On

 

OATBC

Off

 

CCN OARH Broadcast

Off/On

 

OARHBC

Off

 

CCN OAQ Broadcast

Off/On

 

OAQBC

Off

 

Global Schedule Broadcst

Off/On

 

GSBC

Off

 

Daylight Savings Start:

 

 

 

 

 

Month

1 - 12

 

STARTM

4

 

Week

1 - 5

 

STARTW

1

 

Day

1 - 7

 

STARTD

7

 

Minutes to Add

0 - 90

 

MINADD

60

 

Daylight Savings Stop:

 

 

 

 

 

Month

1 - 12

 

STOPM

10

 

Week

1 - 5

 

STOPW

5

 

Day

1 - 7

 

STOPD

7

 

Minutes to Subtract

0 - 90

 

MINSUB

60

Ctlr-ID

Device Name:

A-Series

 

 

 

 

 

 

 

 

Description:

A Series Rooftop

 

 

 

 

Location:

 

 

 

 

 

Software Part Number:

CESR131343-XX-XX

 

 

 

 

Model Number:

 

 

 

 

 

Serial Number:

 

 

 

 

 

Reference Number:

 

 

 

 

HOLIDAY

Broadcast Supervisory

 

 

 

 

HOLDY01S

Holiday Start Month

1-12

 

HOL-MON

0

to

Start Day

1-31

 

HOL-DAY

0

HOLDY30S

Duration (days)

1-99

 

HOL-LEN

0

OCCDEFCS

Occupancy Supervisory

 

 

 

 

 

Timed Override Hours

0

 

OVR-EXT

 

 

Period 1 DOW (MTWTFSSH)

00000000

 

DOW1

 

 

Occupied From

0:00

 

OCCTOD1

 

 

Occupied To

0:00

 

UNOCTOD1

 

 

Period 2 DOW (MTWTFSSH)

00000000

 

DOW2

 

 

Occupied From

0:00

 

OCCTOD2

 

 

Occupied To

0:00

 

UNOCTOD2

 

 

Period 3 DOW (MTWTFSSH)

00000000

 

DOW3

 

 

Occupied From

0:00

 

OCCTOD3

 

 

Occupied To

0:00

 

UNOCTOD3

 

 

Period 4 DOW (MTWTFSSH)

00000000

 

DOW4

 

 

Occupied From

0:00

 

OCCTOD4

 

 

Occupied To

0:00

 

UNOCTOD4

 

 

Period 5 DOW (MTWTFSSH)

00000000

 

DOW5

 

 

Occupied From

0:00

 

OCCTOD5

 

 

Occupied To

0:00

 

UNOCTOD5

 

 

Period 6 DOW (MTWTFSSH)

00000000

 

DOW6

 

 

Occupied From

0:00

 

OCCTOD6

 

 

Occupied To

0:00

 

UNOCTOD6

 

 

Period 7 DOW (MTWTFSSH)

00000000

 

DOW7

 

 

Occupied From

0:00

 

OCCTOD7

 

 

Occupied To

0:00

 

UNOCTOD7

 

 

Period 8 DOW (MTWTFSSH)

00000000

 

DOW8

 

 

Occupied From

0:00

 

OCCTOD8

 

 

Occupied To

0:00

 

UNOCTOD8

 

151

Page 151
Image 151
Carrier 48/50AJ specifications Set Point Table, Config Tables, APPENDIX B — CCN TABLES cont