Carrier 48/50AJ specifications Third Party Control, Demand Controlled Ventilation Control

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 31
Image 31

THIRD PARTY CONTROL

Thermostat — The method of control would be through the thermostat inputs:

Y1 = first stage cooling

Y1 and Y2 = first and second stage cooling

W1 = first stage heating

W1 and W2 = first and second stage heating G = supply fan

Alarm Output — The alarm output TB4-7 and 8, will pro- vide relay closure whenever the unit is under an alert or alarm condition.

Remote Switch — The remote switch may be configured for three different functions. Under ConfigurationUNIT, set RM.CF to one of the following:

0 = no remote switch

1 = occupied/unoccupied switch

2 = start/stop switch

3 = occupancy override switch

With RM.CF set to 1, no time schedules are followed and the unit follows the remote switch only in determining the state of occupancy.

With RM.CF set to 2, the remote switch can be used to shut down and disable the unit, while still honoring time guards on compressors. Time schedules, internal or external, may be run simultaneously with this configuration.

With RM.CF set to 3, the remote input may override an unoccupied state and force the control to go into occupied mode. As with the start/stop configuration, an internal or exter- nal time schedule may continue to control occupancy when the switch is not in effect.

Under ConfigurationSW.LGRMI.L, the remote occu- pancy switch can be set to either a normally open or normally closed switch input. Normal is defined as either unoccupied, start or “not currently overridden,” respective to the RM.CF configuration.

VFD Control — On VFD equipped supply fans, supply duct static pressure control may be left under unit control or be externally controlled. To control a VFD externally with a 4 to 20 mA signal, set SP.RS to 4, under the ConfigurationSP menu. This will set the reset to VFD control. When SP.RS = 4, the static pressure reset function acts to provide direct VFD speed control where 4 mA = 0% speed and 20 mA = 100% (SP.MN and SP.MX will override). Note that SP.CF must be set to 1 (VFD Control) prior to configuring SP.RS = 4. Failure to do so could result in damage to ductwork due to overpressur- ization. In effect, this represents a speed control signal “pass through” under normal operating circumstances. The Com- fortLink controller overrides the third party signal for critical operation situations, most notably smoke and fire control. Wire the input to the controls expansion module (CEM) using TB-11 and 12. An optional CEM board is required.

See Appendix C and the VFD literature supplied with the unit for VFD configurations and field wiring connections to the VFD.

Supply Air Reset — With the installation of the CEM, the ComfortLink controller is capable of accepting a 4 to 20 mA signal, to reset the supply-air temperature up to a maxi- mum of 20 F. See VFD Control section above.

Demand Limit Control — The term “demand limit control” refers to the restriction of the machine’s mechanical cooling capacity to control the amount of power that a machine may use.

Demand limiting using mechanical control is possible via two means:

Two discrete inputs tied to demand limit set point percentages.

OR

A 4 to 20 mA input that can reduce or limit capacity linearly to a set point percentage.

In either case, it will be necessary to install a controls ex- pansion module (CEM).

DEMAND LIMIT DISCRETE INPUTS — First, set DM.L.S in ConfigurationDMD.L to 1 (2 switches).

When InputsGEN.IDL.S1 (Demand Switch no. 1) is OFF, the control will not set any limit to the capacity, and when ON, the control sets a capacity limit to the Configura- tionDMD.LD.L.S1 set point.

Likewise, when InputsGEN.IDL.S2 (Demand Switch no. 2) is OFF, the control will not set any limit to the capacity, and when ON, the control sets a capacity limit to the Configu- rationDMD.LD.L.S2 set point.

If both switches are ON, InputsGEN.IDL.S2 is used as the limiter of capacity.

Under ConfigurationSW.LG, set the logic state appropri- ately for the action desired. Set the DL1.L and DL2.L configu- rations. They can be set normally open or normally closed. For example, if DL1.L is set to OPEN, the user will need to close the switch to cause the control to limit capacity to the demand limit 1 set point. Likewise, if DL1.L is set to CLSE (closed), the user will need to open the switch to cause the control to limit capacity to the demand limit 1 set point.

DEMAND LIMIT 4 TO 20 mA INPUT — Under Configu- rationDMD.L, set configuration DM.L.S to 2 (2 = 4 to 20 mA control). Under the same menu, set D.L.20 to a value from 0 to 100% to set the demand limit range. For example, with D.L.20 set to 50, a 4 mA signal will result in no limit to the capacity and 20 mA signal will result in a 50% reduction in capacity.

Demand Controlled Ventilation Control —

There are multiple methods for externally controlling the econ- omizer damper.

IAQ DISCRETE INPUT CONFIGURATION — The IAQ dis- crete input configuration requires a CEM module (optional) to be installed and an interface to a switch input at TB5-13 and

14.The state of the input on the display can be found at InputsAIR.QIAQ.I.

Before configuring the switch functionality, first determine how the switch will be read. A closed switch can indicate either a low IAQ condition or a high IAQ condition. This is set at ConfigurationSW.LG and IAQ.L. The user can set what a low reading would mean based on the type of switch being used. Setting IAQ.L to OPEN means that when the switch is open the input will read LOW. When the switch is closed, the input will read HIGH. Setting IAQ.L to CLSE (closed) means that when the switch is closed the input will read LOW, and therefore, when the switch is open the switch will read HIGH.

There are two possible configurations for the IAQ discrete input. Select item ConfigurationIAQAQ.CFIQ.I.C and configure for either 1 (IAQ Discrete) or 2 (IAQ Discrete Override).

IQ.I.C = 1 (IAQ Discrete) — If the user sets IQ.I.C to 1 (IAQ Discrete), and the switch logic (ConfigurationSW.LGIAQ.L) is set to OPEN, then an open switch reads low and a closed switch reads high.

If the switch is open, the economizer will be commanded to the IAQ Demand Vent Minimum Position.

These settings may be adjusted and are located at Configura- tionIAQDCV.CIAQ.M.

If the switch is closed, the IAQ reading will be high and the economizer will be commanded to the Economizer Minimum Position.

This setting may be adjusted and is located at Configura- tionIAQDCV.CEC.MN.

31

Page 31
Image 31
Carrier 48/50AJ specifications Third Party Control, Demand Controlled Ventilation Control