CONTROLS SET POINT AND CONFIGURATION LOG

MODEL NUMBER:

 

Software Version

 

SERIAL NUMBER:

 

MBB

CESR131343--

DATE:

 

RCB

CESR131249--

TECHNICIAN:

 

ECB

CESR131249--

 

 

NAVI

CESR131227--

 

 

SCB

CESR131226--

 

 

CEM

CESR131174--

 

 

MARQ

CESR131171--

ITEM

EXPANSION

 

RANGE

DEFAULT

ENTRY

UNIT

UNIT CONFIGURATION

 

 

 

 

C.TYP

Machine Control Type

1

- 6 (multi-text strings)

4

 

CV.FN

Fan Mode (0=Auto, 1=Cont)

0

- 1 (multi-text strings)

1

 

RM.CF

Remote Switch Config

0

- 3 (multi-text strings)

0

 

CEM

CEM Module Installed

Yes/No

No

 

TCS.C

Temp.Cmp.Strt.Cool Factr

0

- 60 min

0

 

TCS.H

Temp.Cmp.Strt.Heat Factr

0

- 60 min

0

 

SFS.S

Fan Fail Shuts Down Unit

Yes/No

No

 

SFS.M

Fan Stat Monitoring Type

0

- 2 (multi-text strings)

0

 

VAV.S

VAV Unocc.Fan Retry Time

0

- 720 min

50

 

SIZE

Unit Size (20-60)

20 - 60

20

 

DP.XR

Disch.Press. Transducers

Yes/No

No

 

SP.XR

Suct. Pres. Trans. Type

0

-1 (multi-text strings)

0

 

RFG.T

Refrig: 0=R22 1=R410A

0

-1 (multi-text strings)

1

 

CND.T

Cnd HX Typ:0=RTPF 1=MCHX

0

-1 (multi-text strings)

0

 

MAT.S

MAT Calc Config

0

- 2 (multi-text strings)

1

 

MAT.R

Reset MAT Table Entries?

Yes/No

No

 

MAT.D

MAT Outside Air Default

0-100%

20

 

ALTI

Altitude……..in feet:

0

- 60000

0

 

DLAY

Startup Delay Time

0

- 900 sec

0

 

STAT

TSTAT_Both Heat and Cool

Yes/No

No

 

AUX.R

Auxiliary Relay Config

0

- 3

0

 

SENS

INPUT SENSOR CONFIG

 

 

 

 

SENSSPT.S

Space Temp Sensor

Enable/Disable

Disable

 

SENSSP.O.S

Space Temp Offset Sensor

Enable/Disable

Disable

 

SENSSP.O.R

Space Temp Offset Range

1

- 10

5

 

SENSRRH.S

Return Air RH Sensor

Enable/Disable

Disable

 

SENSFLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

Disable

 

COOL

COOLING CONFIGURATION

 

 

 

 

Z.GN

Capacity Threshold Adjst

–10 - 10

1

 

MC.LO

Compressor Lockout Temp

–20 - 55 dF

40

 

C.FOD

Fan-Off Delay, Mech Cool

0

- 600 sec

60

 

MLV

Min. Load Valve? (HGBP)

Yes/No

No

 

M.M.

Motor Master Control

Yes/No

No

 

HPSP

Head Pressure Setpoint

80 - 150 dF

113

 

A1.EN

Enable Compressor A1

Enable/Disable

Enable

 

A2.EN

Enable Compressor A2

Enable/Disable

Enable

 

B1.EN

Enable Compressor B1

Enable/Disable

Enable

 

B2.EN

Enable Compressor B2

Enable/Disable

Enable

 

CS.A1

CSB A1 Feedback Alarm

Enable/Disable

Enable

 

CS.A2

CSB A2 Feedback Alarm

Enable/Disable

Enable

 

CS.B1

CSB B1 Feedback Alarm

Enable/Disable

Enable

 

CS.B2

CSB B2 Feedback Alarm

Enable/Disable

Enable

 

REV.R

Rev Rotation Verified ?

Yes/No

No

 

H.SST

Hi SST Alert DelayTime

5

- 30 min

10

 

EDT.R

EVAP.DISCHRGE TEMP RESET

 

 

 

 

RS.CF

EDT Reset Configuration

0

- 3 (multi-text strings)

0

 

RTIO

Reset Ratio

0

- 10

2

 

LIMT

Reset Limit

0

- 20 ^F

10

 

RES.S

EDT 4-20 ma Reset Input

Enable/Disable

Disable

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480077-01

Printed in U.S.A.

Form 48/50A-9T

Pg CL-1

6-10

Replaces: 48/50A-7T

Page 185
Image 185