Carrier 48/50AJ specifications Controls Quick Start

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 27
Image 27
CONTROLS QUICK START

Table 40B — Air Quantity Limits (50AJ,AK,AW,AY,A2,A3,A4,A5)

UNIT

COOLING

 

 

ELECTRIC HEAT

Min CFM

 

Max CFM*

Min CFM

 

Max CFM

 

 

 

50AJ,AW,A2,A3020

6,000

 

10,000

 

 

 

50AK,AY,A4,A5020

4,000

 

10,000

 

 

 

50AJ,AW,A2,A3025

7,500

 

12,500

 

 

 

50AK,AY,A4,A5025

5,000

 

12,500

 

 

 

50AJ,AW,A2,A4027

8,100

 

13,500

 

 

 

50AK,AY,A3,A5027

5,400

 

13,500

6,000

 

15,000

50AJ,AW,A2,A4030

9,000

 

15,000

 

 

 

 

 

50AK,AY,A3,A5030

6,000

 

15,000

 

 

 

50AJ,AW,A2,A4035

10,500

 

17,500

 

 

 

50AJ,AW036

10,500

 

17,500

 

 

 

50AK,AY,A3,A5035

7,000

 

17,500

 

 

 

50AK,AY036

7,000

 

17,500

 

 

 

50AJ,AW,A2,A4040

12,000

 

20,000

 

 

 

50AJ,AW041

12,000

 

20,000

 

 

 

50AK,AY,A3,A5040

8,000

 

20,000

10,500

 

20,000

50AK,AY041

8,000

 

20,000

 

 

 

 

 

50AJ,AW,A2,A4050

13,500

 

20,000

 

 

 

50AK,AY,A3,A5050

10,000

 

20,000

 

 

 

50AJ,AW051

18,000

 

27,000

 

 

 

50AJ,AW,A2,A4060

18,000

 

27,000

15,000

 

27,000

50AK,AY051

12,000

 

27,000

 

 

 

 

 

50AK,AY,A3,A5060

12,000

 

27,000

 

 

 

*Operation at these levels may be limited by entering evaporator air wet bulb temperatures.

CONTROLS QUICK START

The following section will provide a quick user guide to set- ting up and configuring the A Series units with ComfortLink™ controls. See Basic Control Usage section on page 3 for infor- mation on operating the control. For wiring information, refer to unit wiring diagrams in the Major System Components sec- tion on page 101.

IMPORTANT: The ComfortLink controls provide the user with numerous configuration options such as set points, demand levels, reset, and many others. If the building owner or design engineer has not provided specific recom- mendations for these configuration settings, it is suggested that the installer do not make changes to the default factory settings. The factory-configured default values are appro- priate for many applications.

IMPORTANT: The unit is shipped with the unit control disabled. Enable the control by setting Local Machine Dis- able (Service TestSTOP) to No.

Two-Stage Constant Volume Units with Mechanical Thermostat — To configure the unit, per- form the following:

1.The type of control is configured under Configuration UNITC.TYP. Set C.TYP to 4 (TSTAT 2 STG).

2.Remove jumpers from R-W2 and W2-W1 on TB4 in the control box.

3.See Economizer Options section on page 28 for addition- al economizer option configurations.

4.See Exhaust Options section on page 29 for additional exhaust option configurations.

Two-Stage Constant Volume Units with Space Sensor — To configure the unit, perform the following:

1.The type of control is configured under Configuration UNITC.TYP. Set C.TYP to 6 (SPT 2 STG).

2.Under ConfigurationUNITSENSSPT.S, enable the space sensor by setting SPT.S to ENBL (enable).

3.Install jumpers between R-W2 and W2-W1 on TB4 in the control box.

4.The space temperature set points are configured under the Setpoints menu. The heating and cooling set points may

be configured. See the Heating Control and Cooling Control sections on pages 50 and 37 for further descrip- tion on these configurations. The following set points may be configured:

OHSP Occupied Heat Setpoint

OCSP Occupied Cool Setpoint

UHSP Unoccupied Heat Setpoint

UCSP Unoccupied Cool Setpoint

GAP Heat-Cool Setpoint Gap

5.The degrees of demand from the space temperature set points are configured under the ConfigurationD.LV.T submenu. See the Heating Control and Cooling Control sections for further description on these configurations. The following set points may be configured:

L.H.ON Demand Level Lo Heat On

H.H.ON Demand Level Hi Heat On

L.H.OF Demand Level Lo Heat Off

L.C.ON Demand Level Lo Cool On

H.C.ON Demand Level Hi Cool On

L.C.OF Demand Level Lo Cool Off

6.Under ConfigurationUNITCV.FN, set CV.FN to 1 for continuous fan or 0 for automatic fan.

7.To program time schedules, set SCH.N=1 under Config- urationCCNSC.OVSCH.N to configure the control to use local schedules.

8.Under the TimeclockSCH.L submenu, enter the desired schedule. See Time Clock Configuration section on page 75 for further description of these configurations.

9.Under the ConfigurationCCNSC.OV submenu, the following schedules and overrides should be configured:

O.T.L. Override time limit

SPT.O SPT override enabled?

T58.O T58 override enabled?

10.See Economizer Options section on page 28 for addition- al economizer option configurations.

11.See Exhaust Options section on page 29 for additional exhaust option configurations.

27

Page 27
Image 27
Carrier 48/50AJ specifications Controls Quick Start