APPENDIX B — CCN TABLES (cont)

SERVICE-CONFIG TABLES (cont)

TABLE

NAME

 

RANGE

UNITS

POINT NAME

DEFAULT

HEAT

Heating Control Type

0

- 4

 

HEATTYPE

0

 

 

 

Heating Supply Air Setpt

80-120

dF

SASPHEAT

85

 

Occupied Heating Enabled

Yes/No

 

HTOCCENA

No

 

MBB Sensor Heat Relocate

Yes/No

 

HTLATMON

No

 

Fan-off Delay, Gas Heat

45-600

 

GAS_FOD

45

 

Fan-off Delay, Elec Heat

10-600

 

ELEC_FOD

30

 

Staged Gas Heat Type

0

- 4

 

HTSTGTYP

0

 

Max Cap Change per Cycle

5

- 45

 

HTCAPMAX

45

 

S.Gas DB min.dF/PID Rate

0

- 5

 

HT_MR_DB

0.5

 

St.Gas Temp. Dead Band

0

- 5

^F

HT_SG_DB

2

 

Heat Rise dF/sec Clamp

0.05 - 0.2

 

HTSGRISE

0.06

 

LAT Limit Config

0

- 20

^F

HTLATLIM

10

 

Heat Control Prop. Gain

0

- 1.5

 

HT_PGAIN

1

 

Heat Control Derv. Gain

0

- 1.5

 

HT_DGAIN

1

 

Heat PID Rate Config

60 - 300

sec

HTSGPIDR

90

IAQ_

Economizer Min.Position

0

- 100

%

ECONOMIN

5

 

 

IAQ Demand Vent Min.Pos.

0

- 100

%

IAQMINP

0

 

IAQ Analog Sensor Config

0

- 4

 

IAQANCFG

0

 

IAQ 4-20 ma Fan Config

0

- 2

 

IAQANFAN

0

 

IAQ Discrete Input Config

0

- 2

 

IAQINCFG

0

 

IAQ Disc.In. Fan Config

0

- 2

 

IAQINFAN

0

 

OAQ 4-20ma Sensor Config

0

- 2

 

OAQANCFG

0

 

IAQ Econo Override Pos.

0

- 100

%

IAQOVPOS

100

 

Diff.Air Quality LoLimit

0

- 1000

 

DAQ_LOW

100

 

Diff. Air Quality HiLimit

100 - 2000

 

DAQ_HIGH

700

 

DAQ PPM Fan Off Setpoint

0

- 2000

 

DAQFNOFF

200

 

DAQ PPM Fan On Setpoint

0

- 2000

 

DAQFNON

400

 

Diff. AQ Responsiveness

–5 - 5

 

IAQREACT

0

 

OAQ Lockout Value

0

- 2000

 

OAQLOCK

0

 

User determined OAQ

0-5000

 

OAQ_USER

400

 

IAQ Low Reference

0

- 5000

 

IAQREFL

0

 

IAQ High Reference

0

- 5000

 

IAQREFH

2000

 

OAQ Low Reference

0

- 5000

 

OAQREFL

0

 

OAQ High Reference

0

- 5000

 

OAQREFH

2000

 

IAQ Purge

Yes/No

 

IAQPURGE

No

 

IAQ Purge Duration

5-60

min

IAQPTIME

15

 

IAQ Purge LoTemp Min Pos

0-100

%

IAQPLTMP

10

 

IAQ Purge HiTemp Min Pos

0-100

%

IAQPHTMP

35

 

IAQ Purge OAT Lockout

35-70

dF

IAQPNTLO

50

SP__

Static Pres.VFD Control?

No

 

STATICFG

No

 

 

 

Static Pres.Fan Control?

Yes

 

STATPFAN

Yes

 

Static Pressure Sensor

Enable/Disable

 

SPSENS

Disable

 

Static Press. Low Range

–10 - 0

 

SP_LOW

0

 

Static Press. High Range

0

- 10

 

SP_HIGH

5

 

Static Pressure Setpoint

0

- 5

"H2O

SPSP

1.5

 

VFD Minimum Speed

10 - 50

%

STATPMIN

20

 

VFD Maximum Speed

50 - 100

%

STATPMAX

100

 

VFD Fire Speed Override

0

- 100

%

STATPFSO

100

 

Stat. Pres. Reset Config

0-4 (multi-text strings)

 

SPRSTCFG

0

 

SP Reset Ratio ("/dF)

0

- 2.00

 

SPRRATIO

0.2

 

SP Reset Limit in iwc(")

0

- 2.00

 

SPRLIMIT

0.75

 

SP Reset Econo.Position

0

- 100

%

ECONOSPR

5

 

Stat.Pres.PID Run Rate

1

- 200

sec

SPIDRATE

2

 

Static Press. Prop. Gain

0

- 100

 

STATP_PG

20

 

Static Pressure Intg. Gain

0

- 50

 

STATP_IG

2

 

Static Pressure Derv. Gain

0

- 50

 

STATP_DG

0

 

Static Press.System Gain

0

- 50

 

STATP_SG

1

TRIM

Air Temp Lvg SF Trim

–10 - 10

^F

SAT_TRIM

0

 

 

RAT Trim

–10 - 10

^F

RAT_TRIM

0

 

OAT Trim

–10 - 10

^F

OAT_TRIM

0

 

SPT Trim

–10 - 10

^F

SPT_TRIM

0

 

Cir A Sat.Cond.Temp Trim

–30 - 30

^F

SCTATRIM

0

 

Cir B Sat.Cond.Temp Trim

–30 - 30

^F

SCTBTRIM

0

 

Suct.Press.Circ.A Trim

–50 - 50

PSI

SPA_TRIM

0

 

Suct.Press.Circ.B Trim

–50 - 50

PSI

SPB_TRIM

0

 

Dis.Press.Circ.A Trim

–50 - 50

PSI

DPA_TRIM

0

 

Dis.Press.Circ.B Trim

–50 - 50

PSI

DPB_TRIM

0

 

Static Press. Trim (ma)

–2 - 2

 

SPMATRIM

0

 

Bldg. Pressure Trim (ma)

–2 - 2

 

BPMATRIM

0

154

Page 154
Image 154
Carrier 48/50AJ specifications 154, Name Range Units Point Name Default Heat, Trim