Carrier 48/50AJ specifications Staged Gas Heat 48A2,A3,A4,A5 Units, Relay Output Stage

Models: 48/50AJ

1 190
Download 190 pages 18.39 Kb
Page 55
Image 55

Table 69B — Staged Gas Heat — 48A2,A3,A4,A5 Units

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

HEAT CAPACITY

 

UNIT MODEL NO.

 

ConfigurationHEATSG.CF HT.ST

 

POSITION NO. 5

 

ENTRY VALUE

 

 

 

 

 

 

 

 

 

020-030

 

 

Low

 

 

S

1 =

5 STAGE

 

 

 

High

 

 

T

2 =

7 STAGE

 

 

 

 

 

 

 

035-050

 

 

Low

 

 

S

1 =

5 STAGE

 

 

 

High

 

 

T

1 =

5 STAGE

 

 

 

 

 

 

 

060

 

 

Low

 

 

S

 

 

4 = 11 STAGE

 

 

 

High

 

 

T

3 =

9 STAGE

 

 

 

 

 

 

 

Table 70 — Staged Gas Heat Control Steps (ConfigurationHEATSG.CFHT.ST = 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY OUTPUT

 

 

 

 

 

 

STAGE

 

Heat 1

 

Heat 2

 

Heat 3

 

Heat 4

 

Heat 5

 

Heat 6

 

CAPACITY

 

MBB-RLY8

 

MBB-RLY7

 

SCB-RLY1

 

SCB-RLY2

 

SCB-RLY3

 

SCB-RLY4

 

%

 

 

 

 

 

 

 

 

 

 

IGC1

 

MGV1

 

IGC2

 

MGV2

 

IGC3

 

MGV3

 

 

0

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

0

1

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

37

2

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

50

3

 

ON

 

OFF

 

ON

 

OFF

 

OFF

 

OFF

 

75

4

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

87

5

 

ON

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

100

Table 71 — Staged Gas Heat Control Steps (ConfigurationHEATSG.CTHT.ST = 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY OUTPUT

 

 

 

 

 

 

STAGE

 

Heat 1

 

Heat 2

 

Heat 3

 

Heat 4

 

Heat 5

 

Heat 6

 

CAPACITY

 

MBB-RLY8

 

MBB-RLY7

 

SCB-RLY1

 

SCB-RLY2

 

SCB-RLY3

 

SCB-RLY4

 

%

 

 

 

 

 

 

 

 

 

 

IGC1

 

MGV1

 

IGC2

 

MGV2

 

IGC3

 

MGV3

 

 

0

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

0

1

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

25

2

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

33

3

 

OFF

 

OFF

 

ON

 

OFF

 

OFF

 

OFF

 

50

4

 

OFF

 

OFF

 

ON

 

ON

 

OFF

 

OFF

 

67

5

 

ON

 

OFF

 

ON

 

OFF

 

OFF

 

OFF

 

75

6

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

83

7

 

ON

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

100

Table 72 — Staged Gas Heat Control Steps (ConfigurationHEATSG.CTHT.ST = 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY OUTPUT

 

 

 

 

 

 

STAGE

 

Heat 1

 

Heat 2

 

Heat 3

 

Heat 4

 

Heat 5

 

Heat 6

 

CAPACITY

 

MBB-RLY8

 

MBB-RLY7

 

SCB-RLY1

 

SCB-RLY2

 

SCB-RLY3

 

SCB-RLY4

 

%

 

 

 

 

 

 

 

 

 

 

IGC1

 

MGV1

 

IGC2

 

MGV2

 

IGC3

 

MGV3

 

 

0

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

0

1

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

25

2

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

33

3

 

ON

 

OFF

 

ON

 

OFF

 

OFF

 

OFF

 

50

4

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

58

5

 

ON

 

ON

 

ON

 

ON

 

OFF

 

OFF

 

67

6

 

ON

 

OFF

 

ON

 

OFF

 

ON

 

OFF

 

75

7

 

ON

 

OFF

 

ON

 

ON

 

ON

 

OFF

 

83

8

 

ON

 

ON

 

ON

 

ON

 

ON

 

OFF

 

92

9

 

ON

 

ON

 

ON

 

ON

 

ON

 

ON

 

100

55

Page 55
Image 55
Carrier 48/50AJ specifications Staged Gas Heat 48A2,A3,A4,A5 Units, Relay Output Stage