APPENDIX B — CCN TABLES (cont)

MAINTENANCE DISPLAY TABLES

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

ALARMS01

Active Alarm

ascii

 

ALARM_01

 

 

 

 

 

------------------------

ascii

 

 

 

 

Active Alarm

ascii

 

ALARM_02

 

 

------------------------

ascii

 

 

 

 

Active Alarm

ascii

 

ALARM_03

 

 

------------------------

ascii

 

 

 

 

Active Alarm

ascii

 

ALARM_04

 

follow same format for…

------------------------

ascii

 

 

 

 

 

 

 

 

ALARMS02

 

 

 

 

 

ALARMS03

 

 

 

 

 

ALARMS04

 

 

 

 

 

ALARMS05

 

 

 

 

 

COMPRESR

Compressor A1 Relay

On/Off

 

CMPA1

 

 

 

 

 

Compressor A1 Feedback

On/Off

 

CSB_A1

 

 

Curr.Sens.Brd. A1 Status

ascii

 

CSBA1ASC

 

 

CSB A1 Feedback Alarm

Enable/Disable

 

CSB_A1EN

config

 

Comp A1 Locked Out ?

Yes/No

 

CMPA1LOK

 

 

Compressor A1 Strikes

 

 

CMPA1STR

 

 

Enable Compressor A1

Enable/Disable

 

CMPA1ENA

config

 

Compressor A2 Relay

On/Off

 

CMPA2

 

 

Compressor A2 Feedback

On/Off

 

CSB_A2

 

 

Curr.Sens.Brd. A2 Status

ascii

 

CSBA2ASC

 

 

CSB A2 Feedback Alarm

Enable/Disable

 

CSB_A2EN

config

 

Comp A2 Locked Out ?

Yes/No

 

CMPA2LOK

 

 

Compressor A2 Strikes

 

 

CMPA2STR

 

 

Enable Compressor A2

Enable/Disable

 

CMPA2ENA

config

 

Compressor B1 Relay

On/Off

 

CMPB1

 

 

Compressor B1 Feedback

On/Off

 

CSB_B1

 

 

Curr.Sens.Brd. B1 Status

ascii

 

CSBB1ASC

 

 

CSB B1 Feedback Alarm

Enable/Disable

 

CSB_B1EN

config

 

Comp B1 Locked Out ?

Yes/No

 

CMPB1LOK

 

 

Compressor B1 Strikes

 

 

CMPB1STR

 

 

Enable Compressor B1

Enable/Disable

 

CMPB1ENA

config

 

Compressor B2 Relay

On/Off

 

CMPB2

 

 

Compressor B2 Feedback

On/Off

 

CSB_B2

 

 

Curr.Sens.Brd. B2 Status

ascii

 

CSBB2ASC

 

 

CSB B2 Feedback Alarm

Enable/Disable

 

CSB_B2EN

config

 

Comp B2 Locked Out ?

Yes/No

 

CMPB2LOK

 

 

Compressor B2 Strikes

 

 

CMPB2STR

 

 

Enable Compressor B2

Enable/Disable

 

CMPB2ENA

config

DMANDLIM

Active Demand Limit

0-100

%

DEM_LIM

forcible

 

 

Percent Total Capacity

0-100

%

CAPTOTAL

 

 

Demand Limit Select

0-3

 

DMD_CTRL

config

 

Demand Limit Switch 1

On/Off

 

DMD_SW1

forcible

 

Demand Limit Switch 2

On/Off

 

DMD_SW2

forcible

 

Demand Limit Sw.1 Setpt.

0-100

%

DLSWSP1

config

 

Demand Limit Sw.2 Setpt.

0-100

%

DLSWSP2

config

 

4-20 ma Demand Signal

4-20

ma

DMDLMTMA

forcible

 

Demand Limit at 20 ma

0-100

%

DMT20MA

config

 

CCN Loadshed Signal

0-99

 

DL_STAT

 

 

Loadshed Group Number

0-99

 

SHED_NUM

config

 

Loadshed Demand Delta

0-60

%

SHED_DEL

config

 

Maximum Loadshed Time

0-120

min

SHED_TIM

config