APPENDIX B — CCN TABLES (cont)

CONFIG TABLES (cont)

TABLE

NAME

RANGE

UNITS

POINT NAME

DEFAULT

SCHEDOVR

Schedule Number

0-99

 

SCHEDNUM

0

 

 

 

Accept Global Holidays?

Yes/No

 

HOLIDAYT

No

 

Override Time Limit

0-4

hours

OTL

1

 

Timed Override Hours

0-4

hours

OVR_EXT

0

 

Accepting an Override:

 

 

 

 

 

SPT Override Enabled ?

Yes/No

 

SPT_OVER

Yes

 

T58 Override Enabled ?

Yes/No

 

T58_OVER

Yes

 

Allowed to Broadcast a

 

 

 

 

 

Global Sched. Override ?

Yes/No

 

GLBLOVER

No

SET_PNT

 

 

 

 

 

 

Occupied Heat Setpoint

55-80

dF

OHSP

68

 

Occupied Cool Setpoint

55-80

dF

OCSP

75

 

Unoccupied Heat Setpoint

40-80

dF

UHSP

55

 

Unoccupied Cool Setpoint

75-95

dF

UCSP

90

 

Heat-Cool Setpoint Gap

2-10

^F

HCSP_GAP

5

 

VAV Occ. Cool On Delta

0-25

^F

VAVOCON

3.5

 

VAV Occ. Cool Off Delta

1-25

^F

VAVOCOFF

2

 

Supply Air Setpoint

45-75

dF

SASP

55

 

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

 

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

 

Heating Supply Air Setpt

90-145

dF

SASPHEAT

85

 

Tempering Purge SASP

–20-80

dF

TEMPPURG

50

SERVICE-CONFIG TABLES

TABLE

NAME

RANGE

UNITS

POINT NAME

DEFAULT

ALLM

SPT lo alert limit/occ

–10-245

dF

SPLO

60

 

 

SPT hi alert limit/occ

–10-245

dF

SPHO

85

 

SPT lo alert limit/unocc

–10-245

dF

SPLU

45

 

SPT hi alert limit/unocc

–10-245

dF

SPHU

100

 

EDT lo alert limit/occ

–40-245

dF

SALO

40

 

EDT hi alert limit/occ

–40-245

dF

SAHO

100

 

EDT lo alert limit/unocc

–40-245

dF

SALU

40

 

EDT hi alert limit/unocc

–40-245

dF

SAHU

100

 

RAT lo alert limit/occ

–40-245

dF

RALO

60

 

RAT hi alert limit/occ

–40-245

dF

RAHO

90

 

RAT lo alert limit/unocc

–40-245

dF

RALU

40

 

RAT hi alert limit/unocc

–40-245

dF

RAHU

100

 

RARH low alert limit

0-100

%

RRHL

0

 

RARH high alert limit

0-100

%

RRHH

100

 

SP low alert limit

0-5

"H2O

SPL

0

 

SP high alert limit

0-5

"H2O

SPH

2

 

BP lo alert limit

–0.25-0.25

"H2O

BPL

-0.25

 

BP high alert limit

–0.25-0.25

"H2O

BPH

0.25

 

IAQ high alert limit

0-5000

 

IAQH

1200

BP__

Building Press. Config

0-3

 

BLDG_CFG

0

 

 

 

Bldg.Pres.PID Run Rate

5-120

 

BPIDRATE

10

 

Bldg. Press. Prop. Gain

0-5

 

BLDGP_PG

0.5

 

Bldg.Press.Integ.Gain

0-2

 

BLDGP_IG

0.5

 

Bldg.Press.Deriv.Gain

0-5

 

BLDGP_DG

0.3

 

BP Setpoint Offset

0.0 - 0.5

 

BPSO

0.05

 

BP VFD Minimum Speed

0-100

 

BLDGPMIN

10

 

BP VFD Maximum Speed

0-100

 

BLDGPMAX

100

 

VFD/Act. Fire Speed/Pos.

0-100

 

BLDGPFSO

100

 

Power Exhaust Motors

0-2

 

PWRM

1

 

0=None,1=4 Mtr, 2=6 Mtr

 

 

 

 

 

Building Pressure Sensor

Enable/Disable

 

BPSENS

Dsable

 

Bldg Press (+/-) Range

0-1

 

BP_RANGE

0.25

 

Building Pressure Setp.

–0.25 -> 0.25

"H2O

BPSP

0.05

 

Power Exhaust On Setp.1

0-100

%

PES1

35

 

Power Exhaust On Setp.2

0-100

%

PES2

75

 

Modulating PE Alg. Slct.

1-3

 

BPSELECT

1

 

BP PID Evaluation Time

0-10

min

BPPERIOD

1

 

BP Threshold Adjustment

0.1-10

 

BPZ_GAIN

1

 

High BP Level

0-1

 

BPHPLVL

0.05

 

Low BP Level

0-1

 

BPLPLVL

0.04