Table 79 — Economizer Configuration Table

ITEM

EXPANSION

 

 

 

RANGE

 

 

UNITS

CCN POINT

 

DEFAULT

EC.EN

Economizer Installed?

 

Yes/No

 

 

 

ECON_ENA

 

Yes

EC.MN

Economizer Min.Position

 

0

- 100

 

%

 

ECONOMIN

 

5

EC.MX

Economizer Max.Position

 

0

- 100

 

%

 

ECONOMAX

 

98

E.TRM

Economzr Trim For SumZ ?

 

Yes/No

 

 

 

ECONTRIM

 

Yes

E.SEL

Econ ChangeOver Select

 

0

- 3

 

 

 

 

ECON_SEL

 

0

OA.E.C

OA Enthalpy ChgOvr Selct

 

1

- 5

 

 

 

 

OAEC_SEL

 

4

OA.EN

Outdr.Enth Compare Value

 

18 - 28

 

 

 

OAEN_CFG

 

24

 

 

 

 

OAT.L

High OAT Lockout Temp

 

-40 - 120

 

dF

 

OAT_LOCK

 

60

O.DEW

OA Dewpoint Temp Limit

 

50 - 62

 

dF

 

OADEWCFG

 

55

ORH.S

Outside Air RH Sensor

 

Enable/Disable

 

 

 

OARHSENS

 

Disable

E.TYP

Economizer Control Type

 

1

- 3

 

 

 

 

ECON_CTL

 

1

 

 

 

 

 

EC.SW

Economizer Switch Config

 

0

- 2

 

 

 

 

ECOSWCFG

 

0

E.CFG

ECON.OPERATION CONFIGS

 

 

 

 

 

 

 

 

 

 

E.P.GN

Economizer Prop.Gain

 

0.7 -

3.0

 

 

 

EC_PGAIN

 

1

 

 

 

 

 

E.RNG

Economizer Range Adjust

 

0.5 -

5

 

^F

 

EC_RANGE

 

2.5

E.SPD

Economizer Speed Adjust

 

0.1 -

10

 

 

 

EC_SPEED

 

0.75

E.DBD

Economizer Deadband

 

0.1 -

2

 

^F

 

EC_DBAND

 

0.5

UEFC

UNOCC.ECON.FREE COOLING

 

 

 

 

 

 

 

 

 

 

FC.CF

Unoc Econ Free Cool Cfg

 

0-2

 

 

 

 

UEFC_CFG

 

0

 

 

 

 

 

 

FC.TM

Unoc Econ Free Cool Time

 

0

- 720

 

min

 

UEFCTIME

 

120

 

 

 

FC.L.O

Un.Ec.Free Cool OAT Lock

 

40 - 70

 

dF

 

UEFCNTLO

 

50

Custom Psychrometric Curves — Refer to the psychrometric chart and the standard Honeywell A-D curves in Fig. 10. The curves start from the bottom and rise vertically, angle to the left and then fold over. This corresponds to the limits imposed by dry bulb changeover, outdoor enthalpy changeover and outdoor dewpoint limiting respectively. Therefore, it is now possible to create any curve desired with the addition of one outdoor relative humidity sensor and the options for change- over now available. See Fig. 11 for an example of a custom curve constructed on a psychrometric chart.

UNOCCUPIED ECONOMIZER FREE COOLING — This Free Cooling function is used to start the supply fan and use the economizer to bring in outside air when the outside temperature is cool enough to pre-cool the space. This is done to delay the need for mechanical cooling when the system enters the occupied period. This function requires the use of a space temperature sensor.

When configured, the economizer will modulate during an unoccupied period and attempt to maintain space temperature

to the occupied cooling set point. Once the need for cooling has been satisfied during this cycle, the fan will be stopped.

Configuring the economizer for Unoccupied Economizer Free Cooling is done in the UEFC group. There are three configuration options, FC.CF, FC.TM and FC.LO.

Unoccupied Economizer Free Cooling Configuration (FC.CF) — This option is used to configure the type of unoc- cupied economizer free cooling control that is desired.

0 = disable unoccupied economizer free cooling

1 = perform unoccupied economizer free cooling as available during the entire unoccupied period.

2 = perform unoccupied economizer free cooling as available, FC.TM minutes before the next occupied period.

Unoccupied Economizer Free Cooling Time Configuration (FC.TM) — This option is a configurable time period, prior to the next occupied period, that the control will allow unoccu- pied economizer free cooling to operate. This option is only applicable when FC.CF = 2.

A48-7731

Fig. 11 — Custom Changeover Curve Example

62

Page 62
Image 62